1001 reviews | Need a Specific Revision?
HIMA F3322 is a 16-channel digital output module for switching resistive, inductive, and lamp loads in HIQuad safety control systems.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for F3322
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for F3322

  • Manufacturer:
    HIMA
  • Part Number:
    F3322
  • Product Family:
    HIMA HIQuad® X
  • Product Type:
    16-channel digital output module
  • Stock:
    1
  • Output channels:
    16
  • Load types:
    Resistive, inductive, and lamps
  • Maximum channel load:
    500 mA / 12 W
  • Current limiter response:
    > 550 mA
  • Output protection:
    Short-circuit proof
  • L- fault behavior:
    No output signal when L- supply is broken
  • Space requirement:
    4 TE
  • 5 V DC consumption:
    110 mA
  • 24 V DC consumption:
    150 mA plus load
  • Recommended primary rack fuse:
    4 A slow
  • Tariff Code:
    8537101190
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Load Handling Protection Installation Channel Connections

Features:

  • Sixteen solid-state channels for resistive and inductive loads
  • Up to 500 mA per channel, with lamp loads limited to 12 W
  • Current limiting and a defined no-output response if L- is interrupted
Sixteen field commands are concentrated in the four-TE F3322 module, allowing a HIQuad rack to switch actuators without consuming a separate position for every circuit.

A limiter that responds above 550 mA protects each stage; an open L- return suppresses the output rather than leaving the field command in an undefined state.

Rack planning must include the combined load: no more than ten nominally loaded output modules are installed in one I/O subrack, and only half of the possible 8 A total is switched at one time.

HIMA F3322 16-channel digital output module is available through Apter Power for quotation; official HIMA output-module documentation can also be supplied for engineering review.
HIMA F3322 16-channel digital output module Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

F3322 field-load behavior

  • Resistive circuits: Each output can drive a compatible resistive load within the 500 mA and 12 W boundary.
  • Inductive devices: The same channel rating applies to inductive loads used by field actuators.
  • Lamp circuits: Lamp connections are supported when their power remains at or below 12 W.
  • Shared demand: Rack design limits simultaneous switching to half of the possible 8 A aggregate output load.

F3322 protective responses

  • Short circuits: The output stages include current limiting and are described as short-circuit proof.
  • Limiter threshold: Protection responds when channel current rises above approximately 550 mA.
  • Supply interruption: Loss of the L- conductor suppresses output signaling instead of leaving an indeterminate command.
  • Circuit separation: Safety isolation separates the controlled load paths from the module electronics.

F3322 cabinet and plug planning

  • Rack population: One I/O subrack may contain no more than ten output modules at nominal load.
  • Module width: The hardware occupies four TE in the supported HIMA rack.
  • Front connector: Channel conductors terminate through the Z 7136 front cable plug arrangement.
  • Fuse coordination: The standard I/O-rack module fuse is a 4 A slow device for the planned supply branch.

F3322 channel and cable connections

  • Output contacts: Sixteen channels are assigned through the front plug using the designated d and b/x terminal positions.
  • 16-core option: The Z 7136 / 3322 / C.. arrangement uses a LiYY 16 x 0.5 mm² cable with 2.8 x 0.8 mm flat-pin connections.
  • 32-core option: The Z 7136 / 3322 / C.. / P2 arrangement provides the alternative LiYY 32 x 0.5 mm² channel cable.
  • Supply conductors: The L- and L+ paths use the designated z2 and z12 contacts shown in the connection drawings.
Description
Within a HIQuad safety controller, HIMA F3322 is a 16-channel digital output module that switches field loads while preserving protective separation between the control electronics and output circuits.

The channels on F3322 accept resistive or inductive loads up to 500 mA, with a 12 W allowance that also covers compatible lamps. A break in the L- supply prevents an output signal, giving the module a defined behavior for that supply fault.

Short-circuit protection is built into the F3322 output stages, and the current limiter responds above 550 mA. The front cable plug organizes the sixteen channels and the shared load-supply connections for cabinet wiring.

Planning a rack with F3322 requires attention to simultaneous load demand: no more than ten nominally loaded output modules belong in one I/O subrack, and only half of the possible 8 A aggregate load should switch at once.
Alternative Names
F 3322 F-3322 F332 2 HIMA F3322 HIMA-F3322 HIQuad X F3322 HIMA HIQuad X F3322 F33Z2
Technical notes
Rack loading for F3322 must respect the ten-module limit and the restriction that no more than half of the possible 8 A aggregate output load switches simultaneously.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why does F3322 stop producing an output when L- is interrupted?
F3322 deliberately suppresses its output signal after an L- supply break, so troubleshooting should begin with the load-return conductor and its fuse path.
Can F3322 switch a 600 mA solenoid continuously?
F3322 is rated for 500 mA per channel; a 600 mA solenoid exceeds that boundary and requires a different approved interface.
How many F3322 modules can be placed in one I/O subrack at nominal load?
A rack may use no more than ten F3322 modules at nominal output loading, subject to the simultaneous-current restriction.
Why should only part of the F3322 rack load switch at the same time?
For F3322, HIMA limits simultaneous switching to half of the possible 8 A aggregate load to control rack power demand.
Can F3322 drive both lamps and inductive actuators?
F3322 supports resistive and inductive loads up to 500 mA and lamps up to 12 W when the full circuit remains within its ratings.
What should be checked after a F3322 channel reports an overload symptom?
Inspect the F3322 field circuit for a short or excessive load because its current limiter responds above 550 mA.
Which connection point organizes the sixteen F3322 output channels?
The sixteen F3322 channels and their shared L+ and L- connections are organized through the Z 7136 front cable plug.