Honeywell 8C-TAIXA1 51307127-175 is a compact, non-redundant analog input IOTA for 16 single-ended Series 8 channels.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for 8C-TAIXA1 51307127-175
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 8C-TAIXA1 51307127-175

  • Manufacturer:
    Honeywell
  • Part Number:
    8C-TAIXA1 51307127-175
  • Product Family:
    Honeywell Experion PKS ( C200, C300 )
  • Product Type:
    Analog Input Input Output Termination Assembly
  • Stock:
    1
  • Form Factor:
    6-inch compact footprint
  • Architecture:
    Non-redundant, single IOM position
  • Channel Capacity:
    16 single-ended analog inputs
  • Compatible IOMs:
    8C-PAIHA1 or 8C-PAINA1
  • Protective Coating:
    Conformal coated for G3 environment
  • Operating Temperature:
    0°C to +60°C
  • Storage Temperature:
    −40°C to +85°C
  • Relative Humidity:
    5% to 95% non-condensing; derated above 40°C
  • Nominal Supply:
    24 VDC from cabinet distribution
  • Weight:
    0.26 kg
  • Estimated shipping dimensions:
    14.5x12x6.5cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals IOTA Role Channel Mapping Module Pairing Product Applications

Features:

  • Sixteen-channel termination: Provides field connections for 16 single-ended analog input channels.
  • Compact architecture: Uses a 6-inch non-redundant IOTA footprint with one IOM position.
  • Module choice: Supports the documented HART or non-HART Series 8 analog input IOM.
8C-TAIXA1 51307127-175 is the termination assembly beneath a compatible Honeywell Series 8 analog input module.

It carries field wiring and cabinet power; the installed IOM performs signal conversion and channel processing.

Replacement planning should preserve the IOTA/IOM pairing, terminal map, single-module architecture, keying, and cabinet interface.

Apter Power supports 8C-TAIXA1 51307127-175 enquiries with sourcing, documentation, IOM pairing review, and Series 8 configuration guidance.
Honeywell 8C-TAIXA1 51307127-175 Analog Input IOTA Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Field termination: Lands 16 single-ended analog current loops at the Series 8 interface.
  • Mechanical format: The coated 6-inch IOTA provides one nonredundant module position.
  • IOM support: It is documented for both HART and non-HART 16-channel analog input IOMs.
  • Power path: Distributes the cabinet 24 VDC supply through the documented Series 8 arrangement.
  • Channel capacity: The IOTA supports 16 single-ended analog input channels.
  • Signal path: Compatible IOMs accept 4–20 mA from two-wire or self-powered transmitters.
  • Record control: Preserve terminal numbers, field tags, ranges, and control-strategy assignments before removal.
  • Wiring boundary: Field power, shield, grounding, and common connections remain part of the installed cabinet design.
  • HART option: 8C-PAIHA1 is the documented 16-channel HART analog input IOM.
  • Non-HART option: 8C-PAINA1 is the documented 16-channel non-HART analog input IOM.
  • Redundancy boundary: 8C-TAIXB1 is the separate redundant 12-inch IOTA; do not substitute it without cabinet review.
  • Fit control: Verify IOM keying, coating, firmware, cabinet power, and terminal layout before installation.
  • Process measurement: Terminates 4–20 mA transmitter and sensor loops assigned to the compatible Series 8 IOM.
  • Cabinet maintenance: Keeps field wiring fixed when the removable IOM is serviced.
  • HART selection: Supports either HART or non-HART acquisition when paired with the documented IOM.
  • Migration records: Preserves the relationship among field terminals, IOM type, cabinet power, and control strategy.
Description
8C-TAIXA1 51307127-175 is a Honeywell Series 8 analog input I/O Termination Assembly (IOTA). Its compact 6-inch format provides one IOM position for 16 single-ended analog input channels in a non-redundant configuration.

The termination assembly supports the applicable 8C-PAIHA1 HART analog input IOM or 8C-PAINA1 non-HART analog input IOM. 8C-TAIXA1 51307127-175 distributes the cabinet 24 VDC supply and carries field wiring between the terminal interface and the selected IOM.

Because it is an IOTA rather than the signal-processing module, 8C-TAIXA1 51307127-175 should be matched by full part number, IOM type, single-versus-redundant architecture, terminal assignments, cabinet header connection, and Series 8 configuration. Field wiring records should be retained before replacement.
Alternative Names
8C-TAIXA1 51307127-175 8C TAIXA1 51307127 175 8CTAIXA151307127175 Honeywell 8C-TAIXA1 Honeywell 51307127-175 8C-TAIXA1-51307127-175
Technical notes
The 8C-TAIXA1 is a non-redundant 16-channel analog input termination assembly, not the IOM that performs signal conversion. Correct service work matches the IOTA with the selected 8C-PAIHA1 or 8C-PAINA1 module, terminal map, cabinet 24 VDC distribution, keying, and Series 8 configuration before returning the loop to service.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which IOM should be selected for 8C-TAIXA1 51307127-175 in a HART loop?
Use the documented 8C-PAIHA1 HART IOM and verify cabinet keying, firmware, channel configuration, and field power.
Why must terminal mapping be preserved before removing 8C-TAIXA1 51307127-175?
The IOTA is the fixed handoff between field loops and the removable IOM, so a mapping error can move a measurement to the wrong strategy.
How is nonredundant service confirmed for 8C-TAIXA1 51307127-175?
Confirm the 6-inch TAIXA1 architecture; the redundant TAIXB1 uses a different 12-inch arrangement and cabinet layout.
What should be recorded before replacing 8C-TAIXA1 51307127-175?
Record terminal numbers, tags, ranges, shield and common wiring, field power, IOM model, keying, and cabinet position.
Why can a correctly mounted 8C-TAIXA1 51307127-175 still pass no signal?
Incorrect IOM selection, missing field power, wiring polarity, common or shield errors, keying, or channel configuration can interrupt the loop.
How should 8C-TAIXA1 51307127-175 be used with a non-HART loop?
Pair it with the documented 8C-PAINA1 IOM and retain the 4–20 mA channel and cabinet configuration records.