Features:
- Redundant output assembly: The 12-inch IOTA supports a redundant Analog Output arrangement.
- Sixteen 4–20 mA channels: The official guide documents up to sixteen outputs.
- Flexible isolator population: Single-channel MTL4546C and dual-channel MTL4549C options are listed.
CC-GAOX11 routes Series C analog commands through plug-in galvanic isolators to hazardous-area 4–20 mA field devices.
Single-loop integrity favors MTL4546C, while MTL4549C provides two channels per isolator; the fitted population determines cabinet layout.
Replacement preparation should preserve the redundant IOM configuration, HART device records, channel assignment, and open-wire diagnostics.
Availability is subject to Apter Power's current inventory and sourcing confirmation.
Honeywell CC-GAOX11 GI/IS Analog Output IOTA Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell CC-GAOX11 GI/IS Analog Output IOTA Specs
General
- ManufacturerHoneywell
- ModelCC-GAOX11
- ConditionNew Original ready stock
- Product FamilyExperion Series C GI/IS IOTAs
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Redundant output architecture
- IOTA format: Use the official 12-inch redundant assembly.
- IOM arrangement: Confirm both Analog Output IOM positions.
- Channel scope: Keep the configured output count within sixteen.
- Project record: Back up channel and redundancy configuration before replacement.
Supported output devices
- MTL4546C: Use up to sixteen single-channel HART isolators.
- MTL4549C: Use up to eight dual-channel HART isolators.
- Open-wire function: Both listed isolators provide the documented open-wire detection.
- MTL4599: Terminate unused connectors with the dummy isolator when required.
Hazardous-area interface
- Signal type: Use the documented 4–20 mA output channels.
- Intrinsic safety: The supported isolators provide the IS interface.
- Galvanic isolation: The plug-in isolators separate hazardous and safe-area circuits.
- Commissioning: Verify loop polarity, field-device records, and channel diagnostics.