Features:
- Redundant DI termination: The 12-inch IOTA supports a redundant digital input arrangement.
- Thirty-two inputs: Up to 32 high-level 24 V DC signals are documented.
- Line-fault options: MTL4516 and MTL4517 isolators support the documented monitoring functions.
CC-GDIL11 accepts hazardous-area switch or proximity signals and presents isolated solid-state outputs to the associated Series C 24 V DC Digital Input IOM.
The selected isolator changes the usable channel plan: MTL4516 supports 32 channels, while an MTL4517 population is limited to 30 inputs.
Maintenance planning should preserve the isolator layout, line-fault configuration, channel 31 alarm use, and the unavailable channel 32 boundary.
Availability is subject to Apter Power's current inventory and sourcing confirmation.
Honeywell CC-GDIL11 GI/IS Digital Input IOTA Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell CC-GDIL11 GI/IS Digital Input IOTA Specs
General
- ManufacturerHoneywell
- ModelCC-GDIL11
- ConditionNew Original ready stock
- Product FamilyExperion Series C GI/IS IOTAs
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Redundant digital input design
- IOTA size: Use the documented 12-inch assembly.
- IOM arrangement: Confirm both 24 V DC Digital Input IOM positions.
- Input scope: Maintain the approved switch and proximity-detector channel map.
- Project record: Back up redundancy and alarm configuration before replacement.
Isolator-dependent channel plan
- MTL4516: Sixteen isolators support up to 32 inputs.
- MTL4517: Fifteen isolators support only 30 inputs.
- Channel 31: Configure the documented alarm input when line-fault indication is required.
- Channel 32: Do not assign this channel as an input with the MTL4517 arrangement.
Field signal checks
- Signal level: Use the documented 24 V high-level DC input function.
- Device types: Honeywell lists switch and proximity-detector inputs.
- Signal path: The IOTA presents isolated signals to the associated DI IOM.
- Unused slots: Use MTL4599 where the official isolator plan requires a dummy.