Features:
- Sixteen 24 VDC channels for consolidated discrete input acquisition.
- Defined HIGH and LOW thresholds with a typical 10 ms input delay.
- Compact 4 HP, 3U format for compatible Honeywell FSC racks.
Honeywell 10104/2/1 consolidates sixteen 24 VDC digital input channels in one module. It can receive ordinary contact states and discrete operating indications in compatible FSC installations. Because the inputs are not internally tested, the module must not be assigned to fail-safe input functions.
Honeywell 10104/2/1 recognizes a HIGH state above 15 VDC and a LOW state below 9 VDC when input current is below 2 mA. Each input draws 7 mA at 24 VDC, the maximum permitted input voltage is 36 VDC, and the typical input delay is 10 ms.
Honeywell 10104/2/1 occupies 4 TE by 3 HE, equivalent to 4 HP by 3U. It requires FSC software version 3.00 or later and uses the specified A5 and C21 connector coding to support correct rack placement.
The 10104/2/1 Honeywell Digital Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Honeywell 10104/2/1 Digital Input Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell 10104/2/1 Digital Input Module Specs
General
- Manufacturer Honeywell
- Model 10104/2/1
- Condition New Original ready stock
- Product Family 10104/1/1,10101/2/1
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Install Honeywell 10104/2/1 only in an FSC rack position with the correct A5 and C21 connector coding.
- Connect the sixteen field inputs through terminals IN 1 to IN 16 according to the official pin allocation.
- Provide the specified internal and external 24 VDC supplies together with the 5 VDC system supply.
- Use the Honeywell connection drawings for non-redundant, redundant, and FTA-based configurations.
- Acquire ordinary switch, contact, and equipment-status signals in installed FSC systems.
- Monitor non-safety operating states such as running, stopped, open, closed, ready, or alarm.
- Restore standard digital input capacity when maintaining a compatible legacy FSC installation.
- Exclude emergency shutdown or other fail-safe inputs that require internally tested diagnostic channels.
- Use Honeywell 10104/2/1 with FSC software version 3.00 or later.
- Verify that the rack connector uses large coding pins at A5 and C21 before insertion.
- Maintain 5 VDC ripple below 0.5 Vp-p across the specified 0 to 360 Hz range.
- Confirm whether the I/O arrangement is non-redundant or redundant before applying the relevant Honeywell wiring diagram.