1001 reviews | Need a Specific Revision?
The 10105/2/1 is an analog input module with 16 fail-safe (AK5) channels and one external 0–4V readback input, sharing an isolated 0V output.
Get a quick price for 10105/2/1
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 10105/2/1

  • Manufacturer:
    Honeywell
  • Part Number:
    10105/2/1
  • Product Family:
    Honeywell FSC Series
  • Type number:
    10105/2/1 16900
  • Safety class:
    AK1-6 (AK6 in redundant mode)
  • Software Version:
    ≥ 500
  • Space Requirements:
    4 TE, 3 HE (= 4 HP, 3U)
  • Power Requirements:
    5 Vdc 35 mA; 24 Vdc 35 mA
  • Number of Input Channels:
    16
  • Input Range:
    0 to 4.1 V
  • Input Resistance:
    > 1 MΩ
  • A/D Converter:
    12-bit
  • A/D Converter Error:
    ± 1 LSB
  • Module Error:
    < 0.25%
  • Absolute Maximum Input Signal:
    ± 36 Vd
  • Channel Crosstalk:
    > 60 dB
  • Weight:
    0.14 kg
  • Estimated shipping dimensions:
    2x18.8x12.7cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.
Description
The 10105/2/1 analog input module features 16 analog inputs (0-4 V) and one external voltage readback input (0-4 V). These 16 channels are fail-safe (safety class AK5), and all 16 channels share a single isolated analog 0 V output.

The analog inputs of the 10105/2/1 module require conversion of field signals from 0-20 mA to levels usable by the 10105/2/1 module. This conversion can be achieved in two ways:
• Using the FTA-T-14 field termination module, or

• Using the 10105/A/1 analog input conversion module, located on the programming connector (Px) on the back of the 19-inch rack I/O backplane.


Analog input signals (such as thermocouples, PT-100, etc.) can only be used after being converted to 0(4)-20 mA using a dedicated converter (and FTA-T-14 or 10105/A/1 module).
Alternative Names
10201/2/1 10105/2/1 FSC
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Does the 10105/2/1 come with a warranty?
Yes, the 10105/2/1 includes a 1-year free warranty from Apter Power.
What are the power requirements?
This module requires 5 Vdc 35 mA; 24 Vdc 35 mA.
How is the Module Error?
Module Error is < 0.25%.
What inputs are supported?
The 10105/2/1 analog input module has 16 analog inputs (0-4 V) and one external voltage readback input (0-4 V).