Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    For FC-SDI-1648 requirements, Apter Power can provide current pricing and sourcing assistance for the required quantity and delivery schedule.

FC-SDI-1648

/ 4.9
1001 reviews | Need a Specific Revision?
Honeywell FC-SDI-1648 is a 16-channel 48 V DC fail-to-safe digital input module for Honeywell Safety Manager.
In Stock
Ships by Saturday, October 31
Fast Shipping Available
Get a quick price for FC-SDI-1648
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for FC-SDI-1648

  • Manufacturer:
    Honeywell
  • Part Number:
    FC-SDI-1648
  • Product Family:
    Honeywell FSC Series
  • Product Type:
    16-Channel 48 V DC Safe Digital Input Module
  • Stock:
    1
  • Safe input channels:
    16
  • Nominal field voltage:
    48 V DC
  • Maximum signal voltage:
    70 V DC
  • Typical input current:
    4 mA at 48 V DC
  • HIGH threshold:
    Greater than 30 V DC
  • LOW threshold:
    Less than 16 V DC and 1.1 mA
  • Typical input delay:
    10 ms
  • Construction:
    Conformal-coated FC version
  • Tariff Code:
    85389000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Input Data Diagnostics Compatibility Installation Check

Features:

  • Sixteen fail-to-safe 48 V DC inputs
  • Defined HIGH and LOW thresholds
  • Protected 48 V diagnostic test output
FC-SDI-1648 brings sixteen 48 V DC field states into the safety application.

Threshold margin must include supply tolerance, contact resistance, conductor drop and leakage.

The input delay and application time belong in the final safety-response calculation.

The Honeywell FC-SDI-1648 16-Channel 48 V DC Safe Digital Input Module is available for quotation and technical support from Apter Power.
Verified resources for FC-SDI-1648:

Input Data:

  • Safe input channels: 16
  • Nominal field voltage: 48 V DC
  • Maximum signal voltage: 70 V DC
Use the documented FC-SDI-1648 limits when calculating the complete field circuit.

Diagnostics:

  • Logic-state and crosstalk self-tests
  • Protected 48 V test output
  • Typical 10 ms input delay
Resolve all FC-SDI-1648 channel, wiring and system diagnostics before release to operation.

Compatibility:

  • Maximum 70 V DC signal
  • Maximum 100 nF load capacitance
  • Key coding A13/C29
Match FC-SDI-1648 to the approved Safety Manager module, termination and field-device arrangement.

Installation Check:

  • Verify 48 V polarity and range
  • Prove HIGH and LOW thresholds
  • Confirm application mapping
Complete and record the end-to-end functional test after installing FC-SDI-1648.
Description
Honeywell FC-SDI-1648 16-Channel 48 V DC Safe Digital Input Module provides sixteen fail-to-safe 48 V DC digital input channels for Honeywell Safety Manager.

The module recognizes HIGH above 30 V and LOW below 16 V with less than 1.1 mA, with a typical 10 ms delay. Self-tests supervise logic states and crosstalk while a protected 48 V output supports diagnostic testing.

Match field supply, termination, key coding and redundant or non-redundant cabling to the approved design. Prove both logic states, the diagnostic path, application mapping and response time.
Alternative Names
FC-SDI-1648 FC SDI 1648 FCSDI1648 Honeywell FC-SDI-1648 Honeywell FC SDI 1648 Honeywell FCSDI1648 FC-SDI-1648 16-Channel 48 V DC Safe Digital Input Module Honeywell Safety Manager FC-SDI-1648
Technical notes
FC-SDI-1648 monitors sixteen 48 V DC inputs with defined HIGH and LOW thresholds. Verify the exact field interface and approved system configuration before commissioning.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What voltage is recognized as HIGH?
Honeywell documents HIGH above 30 V DC at the module input.
What defines a LOW state?
LOW is below 16 V DC with current below 1.1 mA.
How should the 10 ms delay be used?
Include it with field-device, application and output delays in the safety-response calculation.
Which hardware must be matched with FC-SDI-1648?
Verify Maximum 70 V DC signal, Maximum 100 nF load capacitance and the approved Safety Manager hardware list before installation.
Which diagnostics are important for FC-SDI-1648?
Check logic-state and crosstalk self-tests, protected 48 v test output, typical 10 ms input delay and clear every unexplained channel or system alarm.
Can another construction variant replace FC-SDI-1648?
Only after environmental construction, certifications, hardware revision and project approval have been confirmed.
What commissioning checks are required for FC-SDI-1648?
Perform these product-specific checks: verify 48 v polarity and range, prove high and low thresholds, confirm application mapping; document the final results.
What information is needed to quote FC-SDI-1648?