Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail info@apterpower.com

FBM201D

/ 4.9
1001 reviews | Need a Specific Revision?
Foxboro FBM201D is an eight-channel isolated voltage analog input module for Foxboro DCS field measurements.
In Stock
Ships by Saturday, October 17
Fast Shipping Available
Get a quick price for FBM201D
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for FBM201D

  • Manufacturer:
    Invensys
  • Part Number:
    FBM201D
  • Product Family:
    Foxboro
  • Product Type:
    Eight-Channel Isolated Voltage Analog Input Module
  • Stock:
    1
  • Analog input channels:
    8, individually isolated
  • Input range:
    0 to 10 V DC
  • Input impedance:
    10 MΩ
  • Accuracy:
    ±0.03% of span
  • Temperature coefficient:
    ±50 ppm/°C
  • Common-mode rejection:
    >100 dB at 50/60 Hz
  • Normal-mode rejection:
    >95 dB at 50/60 Hz
  • Heat dissipation:
    3 W maximum
  • Isolation test:
    600 VAC for one minute; input safety limits still apply
  • Power consumption:
    7 W maximum
  • Termination cable:
    Type 1, up to 30 m
  • Module Fieldbus:
    Redundant 2 Mbps
  • Input power:
    24 VDC +5%, -10%
  • Operating temperature:
    -20 to +70°C
  • Storage temperature:
    -40 to +70°C
  • Relative humidity:
    5 to 95%, noncondensing
  • Contamination class:
    ISA-S71.04 Class G3
  • Dimensions:
    4.5 × 10.2 × 10.4 cm
  • Weight:
    0.284 kg
  • Tariff Code:
    8538900000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Signal Matching Termination Commissioning Application
  • Use FBM201D only for its documented FBM201D function and matched field signal type
  • Confirm the exact module order identity, termination assembly and cable before replacement
  • Preserve channel configuration, field wiring and diagnostics before removing FBM201D

Foxboro FBM201D is an eight-channel isolated voltage analog input module for Foxboro DCS field measurements.

FBM201D is the functional FBM201D designation; RH922YK is the current electronic-module part number; RH922ZP / P0926SQ is separate termination hardware.

Before replacement, verify the exact label, signal range, termination assembly, cable, channel configuration, field wiring and system compatibility.

Availability, condition, price, and shipping time for FBM201D are confirmed during quotation.

Foxboro FBM201D Manuals, Datasheets, Links

Important Notice: Other access

  • Match the 0 to 10 V DC source range before wiring
  • Keep each isolated channel within its permitted common-mode conditions
  • Use traceable references for zero and span checks
  • Use the documented RH922ZP / P0926SQ termination assembly
  • Match compression or ring-lug terminals to the installed wiring
  • Keep the Type 1 cable identity and length with the maintenance record
  • Restore channel scaling, alarms and engineering units
  • Check isolation and shield practice before reconnecting field devices
  • Compare module diagnostics with the saved pre-removal state
  • Isolated acquisition of voltage field signals
  • Retrofit of a like-for-like Foxboro DCS input module with preserved scaling
  • Channel-isolated measurements where separate field references must be retained
Description
Foxboro FBM201D is an eight-channel isolated voltage analog input module for Foxboro DCS field measurements.

It converts the documented field signals into isolated digital values for the I/A Series or EcoStruxure Foxboro DCS control database while reporting channel and module diagnostics.

Before installation, verify the exact order-number relationship, signal range, termination assembly, cable type, field power, grounding, saved configuration and baseplate compatibility.
Alternative Names
FBM201D FBM 201D Foxboro FBM201D Invensys FBM201D Invensys Foxboro FBM201D I/A Series FBM201D
Technical notes
FBM201D identifies the FBM201D 0 to 10 V DC input version; its current module part number is RH922YK. The documented TA and 0–10 V scaling must both match the installed loop. Confirm the exact range, TA and Type 1 cable before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can Foxboro FBM201D be used with a 2 to 10 V field device?
Yes, if the channel remains within the documented 0 to 10 V range and the database scaling maps 2 V to the required live-zero value.
Which termination assembly must be matched to Foxboro FBM201D?
Confirm RH922ZP or the documented P0926SQ identity for the installed arrangement, together with the correct Type 1 cable and terminal style.
Why can Foxboro FBM201D saturate before the process reaches full scale?
Check whether the source exceeds 10 V, the field reference is offset, the wrong range is configured, the return path is resistive or the wrong TA/database definition is installed.
Can Foxboro FBM201D reuse wiring from a 0 to 5 V installation?
Only after engineering review. The conductors may be reusable, but the electronics, termination assembly, scaling, alarms and field-device output must all suit 0 to 10 V operation.
What should be checked if one Foxboro FBM201D channel drifts?
Inspect that source and return, terminal resistance, shield and ground path, cable condition, local temperature and channel configuration before replacing the module.
What information should be recorded before replacing Foxboro FBM201D?
Record the RH922YK part label, slot, TA and cable numbers, all channel ranges and scaling, alarm settings, field references, forcing state and diagnostic history.
How should Foxboro FBM201D be accepted after replacement?
Apply known voltages across each used channel's working range, verify polarity and isolation, compare restored scaling and alarms, then observe the real process under controlled conditions.