Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com

140DDI36400

/ 4.9
1001 reviews | Need a Specific Revision?
140DDI36400 is a Modicon Quantum discrete input module with 96 digital inputs designed for 24 V DC operation.
Get a quick price for 140DDI36400
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 140DDI36400

  • Manufacturer:
    Schneider Electric
  • Part Number:
    140DDI36400
  • Product Family:
    Modicon Quantum
  • Group of channels:
    6
  • Logic input:
    Positive (sink)
  • Discrete input voltage:
    24 V DC
  • Input voltage limits:
    19.2...30 V
  • Voltage state 1 guaranteed :
    15...30 V DC
  • Voltage state 0 guaranteed:
    5 V DC
  • Current state 1 guaranteed:
    >= 2.5 mA
  • Current state 0 guaranteed:
    >= 0.7 mA
  • Addressing requirement:
    6 words
  • Input impedance:
    6700 Ohm
  • Weight:
    0.4 kg
  • Estimated shipping dimensions:
    4x10.5x25cm
  • Tariff Code:
    8537101190
  • Country of origin:
    France
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.
Description

The 140DDI36400 is a high-density, low-voltage DC discrete input module for Schneider Electric’s Modicon Quantum automation platform. Delivering 96 galvanically-isolated 24 V DC inputs in a single-slot package, it allows plant designers to consolidate vast numbers of digital signals—push-buttons, proximity switches, photo-cells, valve position sensors—into one compact node, cutting panel footprint, terminal blocks and wiring runs by up to 75 %.


Built for continuous-duty process and discrete applications, the module plugs directly into any Quantum local, remote or distributed-drop rack. Hot-swappable construction and automatic I/O mapping let users add or replace cards without powering down the PLC, eliminating unplanned stops and simplifying maintenance windows. On-board diagnostics report individual channel status, field-power loss and module health to the CPU and SCADA layer via Unity Pro or EcoStruxure™ Control Expert, enabling predictive maintenance and faster fault recovery.


Fully compatible with the entire Quantum portfolio—processors, redundant power supplies, Ethernet RIO, Modbus Plus, Profibus-DP, and high-speed analog modules—the 140DDI36400 scales from stand-alone machines to islanded safety systems and fully redundant SIL-rated architectures. Whether deployed in packaging lines, automotive body shops, material-handling conveyors, water-treatment plants or renewable-energy substations, the module provides the robust, future-proof I/O foundation that modern industrial automation demands.
Alternative Names
140CPS11420 140CPS12420 140XBP00600 140DDO36400 140DDM39000
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What is the absolute maximum input voltage allowed?
30 V continuous; 50 V decaying pulse.
How fast is the response time from state 0 to state 1?
≤ 2 ms.
How fast is the response time from state 1 to state 0?
≤ 3 ms.
What is the module’s base power dissipation, and how much extra for each active point?
1.35 W base + 0.13 W per point that is on.
What isolation voltage can withstand between channel groups?
500 Vrms for 1 minute.
Which LEDs are on the front panel and what do they indicate?
1 green LED: back-plane bus communication present (Active) 1 red LED: external fault detected (F) 96 green LEDs: individual input status
What marking of conformity does the module carry?
CE marking.
How much back-plane current does the module draw?
270 mA.
What mechanical format does the module use?
Standard Quantum module format.