Features:
- Two interface positions accept the redundant IM 153-2 pair.
- The active backplane allows an interface module to be exchanged during RUN.
- A supplied cover protects the interface position when it is not occupied.
6ES7195-7HD10-0XA0 establishes the mechanical and electrical base for the redundant interface pair.
Both IM positions connect to the same ET 200M station path while remaining separately replaceable.
Rail orientation determines the applicable upper ambient-temperature limit.
The Siemens 6ES7195-7HD10-0XA0 ET 200M Redundancy Bus Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7195-7HD10-0XA0 ET 200M Redundancy Bus Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Redundant Interface Positions
- Position one: The first IM 153-2 occupies its dedicated active-bus connector.
- Position two: The second IM 153-2 forms the redundant partner.
- Common station: Both interfaces serve the same downstream ET 200M station.
- Version check: The permitted Bx00 and Bxx1 interface versions must be verified.
Backplane Continuity
- Live backplane: The bus remains available while a supported module is removed.
- Connector alignment: The base fixes each IM connector at the required rail position.
- Expansion: Up to nine active bus modules may be used with a suitable rail.
- Station path: Signal modules remain connected to the ET 200M backplane.
Exchange During RUN
- Preparation: Station diagnostics identify which redundant interface is available for exchange.
- Removal: The active bus permits the selected IM to leave its connector during RUN.
- Insertion: The replacement interface seats into the same keyed position.
- Verification: Redundancy status must return before work on the partner interface.
Rail and Climate Limits
- Rail system: The bus module installs on the ET 200M rail for module change during RUN.
- Cover: The supplied cover closes an unoccupied interface position.
- Horizontal range: Horizontal operation is specified from 0 to 60 °C.
- Vertical range: Vertical operation is specified from 0 to 40 °C.