Features:
- One short-circuit-protected voltage output can use either 1–5 V or -10 to +10 V.
- The TB 16SC connection supports two-wire and four-wire actuator circuits.
- A 5 ms conversion path feeds the output, with settling determined by the connected load.
Siemens 6ES7124-1FA00-0AB0 places one analog voltage-output channel in an ET 200L-SC station.
The selected S5 or S7 representation maps controller data to the configured 1–5 V or -10 to +10 V range.
The output circuit accepts resistive or capacitive loads while short-circuit protection limits fault current.
The Siemens 6ES7124-1FA00-0AB0 article is the single voltage-output submodule; current-output SIMATIC SC versions use different order numbers.
Siemens 6ES7124-1FA00-0AB0 SIMATIC SC 1-Channel Analog Voltage Output Electronic Submodule Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Output Range and Representation
- Range choice: The channel operates at 1–5 V or -10 to +10 V.
- Controller data: The S5 or S7 representation defines the digital value used for conversion.
- Resolution: The configured output uses up to 12 bits including sign.
- Verification: The receiving device range must agree with the module configuration.
Terminal and Field Connection
- Terminal block: The electronic submodule uses the TB 16SC terminal block.
- Actuator circuit: Voltage loads may use two-wire or four-wire connection.
- Cable: Shielded output cable is specified up to 200 m.
- Reference: The load-reference difference must remain within 2 V DC or 2 Vpp AC.
Conversion and Load Response
- Conversion: The channel converts a new output value in 5 ms.
- Resistive load: Settling requires 0.1 ms with a resistive load.
- Capacitive load: Settling extends to 3.3 ms with a capacitive load.
- Load limit: Capacitive loading is permitted up to 1 µF.
Accuracy and Protection Limits
- Linearity: Linearity error is limited to ±0.06% of the output range.
- Temperature: Temperature error is ±0.01%/K of the output range.
- Protection: The voltage output is short-circuit protected with 30 mA maximum short-circuit current.
- Diagnostics: The module does not generate alarms, diagnostics, or substitute values.