Features:
- Eight 24 V DC inputs acquire field states through four double-assigned M12 sockets.
- The integrated PROFIBUS DP slave transfers station input data to the controller.
- Protected 1L+ sensor power and a separate 2L+ load path organize field supply.
Siemens 6ES7141-1BF12-0XB0 combines ET 200X station communication and digital input acquisition.
Each M12 socket on 6ES7141-1BF12-0XB0 carries two channels plus their sensor-supply reference.
The backplane interface of 6ES7141-1BF12-0XB0 extends communication and supply coordination to following modules.
The Siemens 6ES7141-1BF12-0XB0 ET 200X BM 141 Digital Input Basic Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7141-1BF12-0XB0 ET 200X BM 141 Digital Input Basic Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Double-Assigned Digital Inputs
- Socket group: Four M12 sockets carry eight channels by assigning two inputs to each connector.
- Signal levels: The module distinguishes -3 to +5 V as off and 13 to 30 V as on.
- Sensor current: Each active input draws approximately 7 mA at the documented signal level.
- Channel feedback: Individual indicators expose input states before PROFIBUS transfer.
Electronics, Sensors and Load Supply
- Electronics feed: 1L+ powers internal electronics and the encoder-supply outputs.
- Protection: The 1L+ path includes electronic short-circuit and reverse-polarity protection.
- Load feed: 2L+ remains a separate 24 V DC load-voltage connection.
- Fault isolation: Supply indicators separate missing field power from a DP bus fault.
Station Bus Operation
- Slave role: The basic module represents the ET 200X station to the PROFIBUS master.
- Bus rate: Communication supports configured PROFIBUS DP rates up to 12 Mbit/s.
- Addressing: The station address must match the controller hardware configuration.
- Status LEDs: ON, BF, and SF indicators distinguish power, bus, and station faults.
Backplane Growth and Enclosure Integrity
- Expansion count: Up to seven ET 200X expansion modules follow the basic module.
- Backplane path: The internal bus distributes station communication to the connected modules.
- Connector sealing: Unused M12 sockets require protective caps to retain enclosure protection.
- Protection level: Correctly assembled connections support the documented IP66/IP67 rating.