Features:
- The 18.5-inch widescreen presents 1366×768 operator graphics through an analog-resistive touch surface.
- PROFINET and MPI/PROFIBUS DP connect the panel to controller and plant-network paths.
- Two USB ports and two SD-card slots separate peripheral access from removable project storage.
The TP1900 platform combines visualization, alarm handling, recipes, and archives in one cabinet-mounted interface.
A switched Ethernet path and an independent network path let the panel participate in more than one communication arrangement.
Portrait and landscape mounting are both defined, with the permissible operating temperature tied to orientation and tilt.
The Siemens 6AV2124-0UC02-0AX1 TP1900 Comfort Panel may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6AV2124-0UC02-0AX1 TP1900 Comfort Panel Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Operator workspace
- Touch surface: The analog-resistive layer provides the panel's direct process-control input.
- Screen layout: A 1366×768 widescreen supplies space for alarms, trends, and process objects.
- Direct keys: Forty configurable touch buttons can be represented as S7 input signals.
- Backlight: Dimming from 0 to 100 percent adjusts the illuminated display without changing the project resolution.
Controller and Ethernet routes
- Switched ports: Two Ethernet ports form the integrated switch used by the PROFINET connection.
- Independent link: A separate Ethernet interface remains distinct from the switched pair.
- Legacy bus: MPI and PROFIBUS DP traffic use the panel's serial communication path.
- Media redundancy: MRP support allows the Ethernet connection to participate in a managed ring.
Runtime data locations
- Internal area: The 24 MB configuration memory holds the active HMI project.
- Card media: Two SD slots accept removable storage for transfer and archive tasks.
- USB media: USB storage can carry backups or exported runtime data without occupying an SD slot.
- Archive targets: Process and message archives can be directed to a card, USB medium, or Ethernet location.
Cabinet integration checks
- Panel opening: The 465×319 mm cutout receives the aluminum-front housing.
- Rear space: A 73.2 mm mounting depth must remain clear behind the cabinet face.
- Front seal: IP65 and NEMA Type 4/4X apply at the installed front face.
- Orientation limit: Portrait or inclined mounting reduces the maximum ambient temperature from the landscape value.