Features:
- Twelve-inch touch operation presents an 800 × 600 HMI workspace.
- Windows CE separates the panel runtime from controller execution.
- Card slots support CompactFlash and PC Card removable media.
The analog-resistive touch surface provides the primary operator input method for this MP 370 version.
A 64-bit RISC platform runs the visualization project from internal flash memory.
Ethernet, fieldbus, serial and USB paths give the panel distinct roles for control and peripheral communication.
The Siemens 6AV6545-0DA10-0AX0 MP 370 12-inch Touch Multi Panel may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6AV6545-0DA10-0AX0 MP 370 12-inch Touch Multi Panel Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Operator-input behavior
- Touch Surface: Analog-resistive sensing converts screen pressure into an input position.
- Calibration: The runtime calibration aligns the physical touch point with the displayed target.
- Screen Format: The project is composed for an 800 × 600 pixel workspace.
- Color Presentation: The TFT panel renders the configured visualization in 256 colors.
Internal and removable data areas
- Flash Area: Runtime project and user data use the internal 12 MB memory.
- Project Limit: WinCC flexible configurations occupy up to 7 MB of the flash area.
- CompactFlash: One slot accepts supported CompactFlash media.
- PC Card: A separate slot provides the second removable-card format.
Controller-link selection
- Ethernet: The 10/100 interface carries configured TCP/IP communication.
- MPI/PROFIBUS: The fieldbus interface connects the panel to the selected SIMATIC network.
- Serial Links: RS232/TTY and RS422/485 serve their configured peer connections.
- USB Host: Supported peripherals use the host port rather than the PLC network path.
Mechanical and environmental limits
- Panel Opening: The enclosure cutout must match the MP 370 touch-panel dimensions.
- Front Seal: Correct clamping and gasket contact establish IP65/NEMA 4X front protection.
- Rear Space: The IP20 rear area requires clearance for connectors and ventilation.
- Mounting Angle: The permitted angle determines whether the 50 °C or 35 °C operating limit applies.