Features:
- SIMATIC S7-1200 CPU 1211C Compact Controller in a DC/DC/DC configuration.
- Integrated 6 DI at 24 V DC, 4 transistor DO at 24 V DC and 2 AI for 0-10 V signals.
- 75 KB work memory, 1 MB integrated load memory and one 100 Mbit/s PROFINET port.
The
Siemens 6ES7211-1AE40-0XB0 combines CPU processing, onboard I/O and industrial Ethernet communication in a 90 x 100 x 75 mm housing.
Its integrated high-speed inputs and outputs support counting, pulse output and positioning functions for compact automation tasks.
Project selection should confirm the 20.4-28.8 V DC supply, STEP 7 V20 or higher and the required communication-module expansion.
The Siemens 6ES7211-1AE40-0XB0 CPU 1211C Compact Controller is available for quotation, official-document access and sourcing support from Apter Power. OEM status and lead time are confirmed at inquiry.
Siemens 6ES7211-1AE40-0XB0 CPU 1211C Compact Controller Manuals, Datasheets, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Siemens 6ES7211-1AE40-0XB0 CPU 1211C Compact Controller Specs
General
- ManufacturerSiemens
- Model6ES7211-1AE40-0XB0
- ConditionNew Original ready stock
- Product FamilySIMATIC S7-1200 CPU 1211C
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Onboard Signals
- Digital inputs: 6 integrated sourcing/sinking inputs rated for 24 V DC.
- Digital outputs: 4 integrated transistor outputs rated for 24 V DC and 0.5 A.
- Analog inputs: 2 integrated voltage inputs for the 0-10 V range.
- Technology functions: high-speed counting to 100 kHz and four pulse outputs to 100 kHz.
Confirm field wiring, output load and cable shielding against the Siemens datasheet before commissioning.
Industrial Ethernet
- Physical interface: one isolated RJ45 PROFINET port with automatic rate detection.
- Transmission rate: up to 100 Mbit/s on the integrated PROFINET interface.
- PROFINET roles: PROFINET IO Controller and PROFINET IO Device are supported.
- Ethernet protocols: TCP/IP, ISO-on-TCP, UDP, S7 communication and MODBUS are supported.
Optional communication modules are selected separately when a project requires PROFIBUS or AS-Interface connectivity.
Programming and Integration
- Engineering software: STEP 7 V20 or higher is required for this article.
- Programming languages: LAD, FBD and SCL are supported.
- Local expansion: the CPU supports one signal or communication board and up to three communication modules.
- Installation: IP20 protection with a horizontal operating range from -20 to +60 °C.
Match the hardware catalog entry, firmware V4.7 and project security settings before downloading a program to the controller.