Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power supports 6DS1603-8BA document review, configuration matching and quotation.

6DS1603-8BA

/ 4.9
1001 reviews | Need a Specific Revision?
Siemens 6DS1603-8BA is a TELEPERM M card with 32 protected, non-isolated 24 V DC binary outputs rated 100 mA per channel. Four eight-output groups support dense low-current command functions.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for 6DS1603-8BA
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 6DS1603-8BA

  • Manufacturer:
    Siemens
  • Part Number:
    6DS1603-8BA
  • Product Family:
    Siemens Teleperm
  • Product Type:
    Binary Output Module
  • Stock:
    1
  • Output channels:
    32 non-isolated outputs
  • Nominal output voltage:
    24 V DC
  • Supply range:
    20 to 33 V DC
  • High output level:
    15 to 33 V
  • Rated output current:
    100 mA per output
  • Output protection:
    Short-circuit protected
  • Maximum switching frequency:
    2 Hz
  • Module fuse:
    4 A
  • Output grouping:
    4 groups of 8 outputs
  • Supply ripple:
    Less than 15%
  • 5 V bus range:
    4.75 to 5.25 V
  • PM current:
    Approximately 60 mA
  • Low output level:
    0 to 2.5 V
  • Output fault behavior:
    Reset or hold selectable after controller failure
  • Board format:
    233.4 x 160 mm
  • Tariff Code:
    8537101190
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Applications Performance Installation Protection

Features:

  • Thirty-two 24 V DC semiconductor outputs are arranged in four non-isolated groups of eight.
  • Each protected channel is rated 100 mA and the module uses a 4 A fuse.
  • Output reset or hold behavior can be selected for loss of controller control.
The BA execution is the lower-current, high-density output card intended for a common 24 V field system.

Controller bits drive protected electronic switches that distribute the external L+ supply to assigned loads.

Check bank current, inductive suppression, common return integrity and failure-state configuration before any field command is enabled.

Apter Power can support exact-model configuration review and quotation for Siemens 6DS1603-8BA.
Verified resources for Siemens 6DS1603-8BA: Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Large indication panels can be driven directly when every lamp or interface load remains below the channel rating.
  • Interposing relays can translate the electronic outputs into isolated higher-power contacts for external equipment.
  • Small solenoid or pilot circuits can be consolidated where the 2 Hz switching limit meets the process requirement.
  • Thirty-two electronic channels issue discrete commands from a TELEPERM M rack to low-current field loads.
  • Common reference wiring, load suppression, bank current and the 2 Hz switching limit must be checked before commissioning.
  • Each output can deliver up to 100 mA for suitable 24 V DC devices without exceeding the permitted group loading.
  • Thirty-two non-isolated electronic outputs share the prescribed reference arrangement for cabinet field wiring.
  • The 24 V DC nominal output is intended for compatible low-current actuators, indicators and interface circuits.
  • An external supply between 20 and 33 V DC must be connected with the correct polarity and conductor protection.
  • A 4 A module fuse protects the output supply path against excessive current in the connected field circuits.
  • Short-circuit-protected electronic channels limit fault propagation when an output conductor or load becomes defective.
  • The 15 to 33 V high-state range helps verify that an energized command remains within the valid output level.
Description
6DS1603-8BA converts TELEPERM controller decisions into thirty-two semiconductor output commands. Four banks of eight share the 24 V supply and reference, providing compact control of interposing relays, indicators and other low-current loads that remain within the channel and bank limits.

Each channel is short-circuit protected and produces the 0–2.5 V low state or 15–33 V high state. The module's controller-failure behavior can be selected so outputs reset or retain their last image, a decision that directly affects the safe response of connected equipment.

Commissioning should calculate simultaneous loading and verify suppression for inductive devices even though the channels are protected. Common reference wiring, 4 A module fuse, 2 Hz switching ceiling and the configured failure response must match the original control philosophy.
Alternative Names
6DS1603-8BA 6DS1603 8BA 6DS16038BA Siemens 6DS1603-8BA Siemens 6DS1603 8BA 6DS1603-8BA Binary Output Module Siemens 6DS1603-8BA TELEPERM M 6DS1603-8BA Catalog Number
Technical notes
Confirm whether 6DS1603-8BA is configured to reset or hold outputs after controller failure; changing that choice during replacement can alter the plant's fail-state behavior.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What type of load is appropriate for one 6DS1603-8BA output?
Use a 24 V DC load that stays within 100 mA and follows the module's common-reference and switching-frequency limits.
How does 6DS1603-8BA respond to an output short circuit?
Its semiconductor channels are protected, but the fault must still be cleared and the bank and module fuse checked.
Can 6DS1603-8BA be used as a fast pulse-output card?
The card is intended for discrete commands rather than high-speed pulse generation; faster cycling falls outside the duty.
Which failure-state choice must be retained on 6DS1603-8BA?
The project may select reset or hold when controller control is lost, and that safety behavior must be matched.
What should be calculated before adding loads to 6DS1603-8BA?
Evaluate each channel, each eight-output bank, the common return, module fuse and inrush or suppression requirement.
How should the fail-state and load schedule be packaged for a 6DS1603-8BA enquiry?
Provide the output schedule, rack drawing, connector pinout, fuse data, fail-state setting and photographs of the installed module.

Product Browsing History