Technical specifications for AAV141-S50/K4A00

  • Manufacturer:
    Yokogawa
  • Part Number:
    AAV141-S50/K4A00
  • Product Family:
    Centum CS-Centum VP
  • Product Type:
    Analog Input Module
  • Stock:
    1
  • Channels:
    16 non-isolated inputs
  • Input Signal:
    1-5 V DC
  • Adapter:
    ATK4A-00 KS cable interface adapter
  • Environmental Option:
    basic type with no explosion protection
  • Update Period:
    10 ms
  • Accuracy:
    +/-4 mV
  • Weight:
    0.44 lbs (0.2 kg)
  • Estimated shipping dimensions:
    32.8 x 130 x 107.5 mm
  • Tariff Code:
    Please confirm the destination before shipping.
  • Country of origin:
    Japan
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Voltage Input KS Interface Redundant Use

Features:

  • Channels: 16 non-isolated inputs
  • Input Signal: 1-5 V DC
  • Adapter: ATK4A-00 KS cable interface adapter
The AAV141-S50/K4A00 ordering code selects standard 16-channel non-isolated 1-5 V DC input module with basic non-explosion type and ATK4A-00 KS cable adapter.

It converts sixteen 1-5 V DC field signals for the documented CENTUM VP analog input path.

Verify the 1-5 V range, ATK4A-00 interface, and supported redundant arrangement before wiring.

Availability is subject to Apter Power inventory and sourcing confirmation.
Yokogawa AAV141-S50/K4A00 Specifications

General

  • ManufacturerYokogawa
  • ModelAAV141-S50/K4A00
  • ConditionNew and factory sealed
  • Product FamilyCENTUM VP Analog I/O Modules
  • Allowable Input: +/-7.5 V maximum
  • Impedance: 1 Mohm or greater while powered
  • Common Mode: +/-1 V or less
  • Adapter: ATK4A-00 included by /K4A00
  • Field Route: connect through the documented KS cable path
  • Termination: verify the mating terminal board before wiring
  • Pairing: dual-redundant module configuration is supported
  • Channel Match: both modules require matching channel engineering
  • Switchover: validate inputs after redundant changeover
Description
Yokogawa AAV141-S50/K4A00 is an analog input module. Standard 16-channel non-isolated 1-5 V DC input module with basic non-explosion type and ATK4A-00 KS cable adapter.

It converts sixteen 1-5 V DC field signals for the documented CENTUM VP analog input path.

Verify the 1-5 V range, ATK4A-00 interface, and supported redundant arrangement before wiring.
Alternative Names
AAV141S50K4A00 AAV141 S50 K4A00 Yokogawa AAV141-S50/K4A00 AAV141-S50 Analog Input Module AAV141-S50/K4A00 module
Technical notes
AAV141-S50/K4A00 requires 1-5 V DC signals and the ATK4A-00 KS interface specified by Yokogawa.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How many voltage channels can AAV141-S50/K4A00 scan?
Yokogawa specifies 16 non-isolated inputs for AAV141-S50/K4A00.
What transmitter signal range should feed AAV141-S50/K4A00?
For AAV141-S50/K4A00, the official input signal is 1-5 V DC.
Which KS interface adapter belongs with AAV141-S50/K4A00?
The official specification lists ATK4A-00 KS cable interface adapter under adapter.
Does the S50 configuration include explosion protection?
AAV141-S50/K4A00 uses basic type with no explosion protection for this configuration.
How quickly does AAV141-S50/K4A00 refresh input values?
Yokogawa documents 10 ms as the update period.
What reference accuracy is specified for AAV141-S50/K4A00?
This order code is specified with +/-4 mV.