Technical specifications for ADR541-P50

  • Manufacturer:
    Yokogawa
  • Part Number:
    ADR541-P50
  • Product Family:
    Centum CS-Centum VP
  • Product Type:
    Relay Output Module
  • Stock:
    1
  • Number of Output Channels:
    16
  • Rated Applied Voltage:
    24–110 VDC; 100–240 VAC
  • Status Output Response:
    12 ms or less
  • Mixed Output Response:
    20 ms or less
  • Pulse Width:
    40 ms–7200 s
  • Relay Switching Life:
    100,000 operations
  • External Connection:
    Pressure clamp terminal; AKB334 cable
  • Weight:
    0.3 kg
  • Estimated shipping dimensions:
    3.28 × 10.75 × 13.0 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    Japan
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Contact Ratings Output Functions Connection

Features:

  • 16 isolated relay output channels.
  • Rated for 24–110 VDC or 100–240 VAC circuits.
  • Supports status, pulse-width, and time-proportioning outputs.
  • Can be used in a dual-redundant configuration.
Yokogawa ADR541-P50 supplies 16 relay contact outputs for compatible DC or AC field circuits in an FIO node.

The module uses common minus wiring every eight channels, with a maximum total current of 8 A allowed per common.

Current OEM lifecycle classification for ADR541-P50 is not stated in the available manufacturer documentation. Availability is confirmed during quotation.
Yokogawa ADR541-P50 Relay Output Module Specs

General

  • Manufacturer Yokogawa
  • Model ADR541-P50
  • Condition New Original ready stock
  • Product Family CENTUM VP FIO
  • Resistive load at 24 VDC: 2.0 A per channel.
  • Resistive load at 110 VDC: 0.4 A per channel.
  • Resistive load at 100 or 220 VAC: 2.0 A per channel.
  • Maximum total current per common: 8 A.
  • ON/OFF status output function.
  • One-shot pulse-width output function.
  • Time-proportioning ON/OFF function.
  • Relay switching life: 100,000 operations.
  • External connection: pressure clamp terminal or dedicated AKB334 cable.
  • Compatible single pressure clamp terminal block: ATC4S.
  • Compatible terminal board: AEC4D through the AKB334 cable.
  • Connect a spark-killer diode when driving a DC relay.
Description

Yokogawa ADR541-P50 is a 16-channel isolated relay output module for FIO. The P50 suffix specifies pulse-width and time-proportioning output functions, no status display, no explosion protection, and the basic type.

The module switches 24–110 VDC or 100–240 VAC relay contact signals. It supports status, one-shot pulse-width, and time-proportioning ON/OFF output functions.

The module supports dual-redundant configuration and connects through a pressure clamp terminal or the dedicated AKB334 cable.

Alternative Names
ADR541-P50 ADR541 P50 ADR541P50 Yokogawa ADR541-P50 Yokogawa ADR541 P50 YOKOGAWA ADR541P50 ADR541-P50 Relay Output Module ADR541 P50 FIO Module
Technical notes
Yokogawa ADR541-P50 provides 16 isolated relay outputs for 24–110 VDC or 100–240 VAC circuits. Confirm the P50 suffix, load type, common current, and connection method before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What is the function of Yokogawa ADR541-P50?
It provides 16 isolated relay contact outputs for compatible DC or AC field circuits in a Yokogawa FIO system.
What voltage range does ADR541-P50 support?
Yokogawa specifies 24–110 VDC and 100–240 VAC at 50/60 Hz.
What does the P50 suffix mean on ADR541-P50?
It identifies pulse-width and time-proportioning output functions, no status display, no explosion protection, and the basic type.
Can ADR541-P50 be used in a redundant configuration?
Yes. Yokogawa states that ADR541 can be used in a dual-redundant configuration.
What should be checked before replacing ADR541-P50?
Verify the complete suffix, AC or DC load type, current per channel and common, terminal or cable connection, and redundancy arrangement.
What is the current OEM lifecycle status of ADR541-P50?
A current OEM lifecycle classification is not stated in the available Yokogawa documentation; availability is confirmed during quotation.
How can I request an ADR541-P50 manual, price, and availability?
Contact Apter Power with the complete model, required quantity, load details, and system configuration for documentation and a quotation.