Features:
- Sixteen Individually Isolated TC/mV Input Channels
- Supports Eight Thermocouple Types and Two Millivolt Ranges
- Cold-Junction Compensation with Configurable Burnout Direction
The Yokogawa AST143-S00 acquires thermocouple and low-level millivolt signals for FIO Field Control Units. Each of its sixteen isolated channels can be selected for the supported TC type or mV range.
Cold-junction compensation and selectable UP or DOWN burnout behavior support controlled temperature measurement. The built-in barrier separates the field interface from the system.
Before ordering the Yokogawa AST143-S00, confirm the complete suffix code, channel requirements, terminal block, and Field Control Unit configuration.
Yokogawa AST143-S00 Manuals, Datasheets, Drivers, Link
Important Notice: Manuals, accessories, cables, calibration data, and software are not included unless specifically listed in the quotation or product description. Please confirm documentation and accessory requirements before ordering.
Yokogawa AST143-S00 TC/mV Input Module with Built-In Barrier Specs
General
- Manufacturer Yokogawa
- Model AST143-S00
- Condition New Original ready stock
- Product Family AST143-S00, AST143, FIO Built-In Barrier Modules
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Sixteen isolated input channels
- Thermocouple types: B, E, J, K, N, R, S, and T
- Millivolt ranges: -100 to 150 mV and -50 to 75 mV
- Input type can be selected individually by channel
- Input resistance: 1 MΩ minimum
- TC accuracy: ±40 µV at 23 °C
- mV accuracy: ±80 µV at 23 °C
- Update period: 1 second maximum
- Specified for Zone 2 or Division 2 installation
- Pressure clamp terminal connection through ATST4□
- Operating ambient temperature: -20 to 70 °C
- Approximate module dimensions: 32.8 × 107.5 × 130 mm