Features:
- Positions the sensing tip at a documented 6.5 in penetration.
- Routes a 0.5 m probe lead through the package 03 sealing arrangement.
- Provides 303/304 stainless-steel construction for a durable external mounting point.
The 065 field distinguishes this medium-depth housing from shorter and longer 24701 assemblies.
Its sleeve guides the probe toward the shaft target while the outer housing protects adjustment and connection hardware.
Selection must retain the controlled standoff, mounting thread and drawing reference in addition to the visible penetration.
Apter Power can review sourcing, documentation and system matching for 24701-28-05-XX-065-03-XX MOD 323933-00-02.
Verified resources for Bently Nevada 24701-28-05-XX-065-03-XX MOD 323933-00-02:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Pump and compressor bearing cases can use the assembly where a 6.5 in reach is required to view the shaft.
- Oil-system machinery can benefit from the seal-grip fittings when routing the probe lead out of the housing.
- Service work can restore the same sensing geometry after a probe is removed for inspection.
- The stainless-steel housing is intended for external industrial machine installations exposed to normal plant contaminants.
- Thread sealing and cover closure should prevent oil mist or moisture from reaching the probe connection.
- Vibration at the bracket must be minimized so housing motion does not appear as shaft displacement.
- Stable gap readings require a rigid sleeve, secure probe lock and intact connector insulation.
- A drifting signal can indicate loose mounting, connector contamination or an incorrect probe depth.
- The external enclosure protects the connection but does not replace transducer-system electrical diagnostics.
- The 6.5 in penetration is a mechanical configuration and must match the machine drawing before gap adjustment.
- Monitor channel setup must correspond to the installed 3300 XL 8 mm transducer system and its electrical length.
- Alarm and scale settings are established in the monitoring system, not in the passive housing assembly.