Features:
- Accepts 85-264 VAC or 100-250 VDC through a reinforced-isolation input stage.
- Maintains at least 20 ms hold-up at full load and automatically recovers from a continuous short circuit.
- Signals output health through front and side green LEDs plus a 30 VDC, 1 A power-OK relay contact.
The current ordering configuration is 60X/XPS01-01, a 240 W AC/DC supply reserved for the Orbit 60 3U chassis and identified by approval code 01.
It provides a regulated 24 VDC chassis source with active power-factor correction, low input inrush, and temporary 150% output capability for short starting loads.
Before commissioning, verify the incoming source, PE connection, external protection, output trim, cabinet airflow, and hazardous-area temperature limits against the installation drawing.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Bently Nevada 60X/XPS01-01:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Supplies regulated 24 VDC power to a compatible 3U Orbit 60 machinery-protection chassis.
- Supports industrial cabinets that require either 85–264 VAC or 100–250 VDC input flexibility.
- Provides short-duration current boost for startup events while returning automatically to the continuous output limit.
- Active power-factor correction supports a power factor of up to 98 percent while reducing unnecessary input-current demand.
- Typical conversion efficiency reaches 95 percent, allowing the 240 W supply to use a compact DIN-rail format.
- A 150 percent current boost is available for four seconds before the controlled protection and restart sequence takes effect.
- The -01 ordering suffix identifies the CSA/NRTL/C Class I, Division 2 version of the 240 W industrial power supply.
- The design follows the applicable IEC and EN industrial electromagnetic-compatibility and electrical-safety requirements.
- Approval suitability depends on the complete product marking and the installation conditions specified for the certified enclosure.
- Short-circuit, overload, overvoltage and overtemperature functions protect the supply through automatic recovery or a controlled restart.
- Reinforced input-to-output insulation is tested at 3,000 VAC for sixty seconds as part of the documented isolation design.
- Protective-earth connection is mandatory because the unit is prepared as Class I equipment within the Orbit 60 power arrangement.