- DeltaV M-series PROFIBUS DP Interface Card Series 2 hardware
- One RS-485 two-wire master segment for distributed slave devices
- Device configuration uses manufacturer-supplied PROFIBUS GSD files
KJ3243X1-BA1 is an Emerson DeltaV M-series PROFIBUS DP Interface Card Series 2 for integrating distributed field devices.
The card operates as the master for a single RS-485 segment and exchanges configured cyclic input and output data with PROFIBUS DP slave devices.
Before installation or replacement, verify the complete card number, Series 2 carrier and terminal arrangement, DeltaV software, GSD files, slave addresses, network rate, cable, shield, and termination.
Availability, condition, price, and shipping time for KJ3243X1-BA1 are confirmed during quotation.
Emerson KJ3243X1-BA1 PROFIBUS DP Interface Card Series 2 Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- The interface provides one PROFIBUS DP master segment
- RS-485 two-wire communication is used for the fieldbus physical layer
- As many as 64 configured slave devices are supported on the segment
- Each slave is defined with its manufacturer-supplied GSD file
- Input and output data are mapped cyclically between the slaves and DeltaV
- Bus address, data rate, and module layout must match the installed project
- Maximum segment length is 1200 m at rates through 93.75 kbit/s
- Maximum segment length is 1000 m at 187.5 kbit/s and 400 m at 500 kbit/s
- Maximum segment length is 200 m at 1500 kbit/s
- DeltaV communication with PROFIBUS-compatible remote I/O stations
- Integration of PROFIBUS motor-control and drive devices into process control
- Cyclic exchange with PROFIBUS-compatible discrete actuators and sensors