Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com

VE4005S2B1

/ 4.9
1001 reviews | Need a Specific Revision?
Emerson VE4005S2B1 is an 8-channel DeltaV M-series 4–20 mA HART analog-output assembly with standard I/O termination.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for VE4005S2B1
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for VE4005S2B1

  • Manufacturer:
    Emerson
  • Part Number:
    VE4005S2B1
  • Product Family:
    DeltaV
  • Product Type:
    8-Channel 4–20 mA HART Analog Output Assembly with Standard I/O Termination Block
  • Stock:
    1
  • Number of Channels:
    8
  • Nominal Signal Range:
    4–20 mA
  • Full Signal Range:
    1–23 mA
  • Termination:
    Standard I/O termination block
  • Channel Isolation:
    Each channel optically isolated from the system; factory tested at 1500 V DC
  • Resolution:
    12 bit
  • Accuracy:
    0.25% of span
  • Output Compliance:
    20 mA at 21.6 V DC into 700 Ω
  • LocalBus Current:
    100 mA typical; 150 mA maximum at 12 V DC nominal
  • Field Circuit Power:
    300 mA maximum at 24 V DC ±10%
  • Card Keying:
    A4
  • Minimum DeltaV Release:
    Version 10.3.1
  • Tariff Code:
    9032900090
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Termination Compatibility Commissioning Application
  • DeltaV M-series Traditional I/O assembly with eight HART analog-output channels
  • Standard I/O termination block configuration with A4 card keying
  • Per-channel system isolation and card-stored calibration information

VE4005S2B1 supplies eight commanded current loops for compatible DeltaV M-series field devices.

The complete assembly depends on the correct carrier, terminal block, keying, field supply, wiring, database assignment, and supported DeltaV software level.

Confirm loop polarity, load resistance, grounding, HART device configuration, and output validation requirements before commissioning.

Availability, condition, price, and shipping time for VE4005S2B1 are confirmed during quotation.

Emerson VE4005S2B1 DeltaV HART Analog Output Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • VE4005S2B1 uses the documented standard I/O termination block
  • VE4035S2B1 is the separate redundant standard-termination ordering option
  • VE4005S2B2 and VE4005S2B3 identify fused and 16-pin mass-termination alternatives
  • Supported with DeltaV M-series horizontal and VerticalPlus carrier architecture
  • M-series horizontal carriers are not physically compatible with S-series horizontal carriers
  • The documented VE4005S2B1 configuration requires DeltaV version 10.3.1 or later
  • Restore the approved channel database and HART device definitions
  • Check current-loop polarity, field supply, load resistance, and grounding
  • Validate commanded current and HART communication on every enabled channel
  • Driving eight 4–20 mA final-control or indication loops from DeltaV M-series I/O
  • Supporting HART communication with compatible field devices on the configured output channels
  • Maintaining standard-termination DeltaV installations that specify the VE4005S2B1 order code
Description
VE4005S2B1 is an Emerson DeltaV M-series Traditional I/O assembly that combines an eight-channel 4–20 mA HART analog-output card with a standard I/O termination block.

Each output channel is optically isolated from the system, and the card stores its calibration information for supported replacement and maintenance procedures.

Before replacement, verify the M-series carrier, A4 keying, function and field-wiring keys, terminal block, loop supply, load resistance, DeltaV release, channel database, and HART device definitions.
Alternative Names
VE4005S2B1 VE4005 S2 B1 VE4005-S2-B1 Emerson VE4005S2B1 DeltaV VE4005S2B1 Emerson DeltaV VE4005S2B1 VE4005S2B1 HART Analog Output
Technical notes
Emerson VE4005S2B1 requires DeltaV version 10.3.1 or later, A4 card keying, a standard I/O termination block, and verification of all eight loop assignments and HART devices.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Is Emerson VE4005S2B1 the redundant version of this DeltaV output assembly?
No. VE4005S2B1 is the standard non-redundant configuration. VE4035S2B1 is the documented redundant standard-termination order code.
Can Emerson VE4005S2B1 replace a fused or mass-termination version directly?
Not without engineering review. VE4005S2B2 and VE4005S2B3 use different termination arrangements, so the installed terminal hardware and wiring must be checked.
What keying must be verified before installing Emerson VE4005S2B1?
Verify A4 card keying together with the function and field-wiring keys on the installed carrier and terminal block.
Will Emerson VE4005S2B1 retain its calibration after replacement?
The card stores calibration information. Follow the approved DeltaV replacement procedure and validate each output loop after installation.
What should be checked when a VE4005S2B1 loop cannot reach its commanded current?
Check field-supply voltage, loop polarity, wiring continuity, load resistance, grounding, channel configuration, and the connected field device.
Can Emerson VE4005S2B1 be installed on an S-series horizontal carrier?
No. Emerson states that M-series and S-series horizontal controller carriers are not physically compatible.
What details should be provided when ordering Emerson VE4005S2B1?
Provide the complete order code, existing card and terminal-block labels, carrier type, DeltaV version, redundancy requirement, quantity, condition, and clear wiring photos.