Features:
- Accepts RTD temperature sensors through one individually characterized field channel.
- Supports 2-wire, 3-wire, and 4-wire RTD connections for flexible field wiring.
- Performs high-resolution temperature measurement within the DeltaV CHARM I/O architecture.
KL3031X1-BA1 combines sensor type of RTD input, sensor wiring of 2-wire, 3-wire, or 4-wire, and channels of One characterized field channel in the DeltaV Electronic Marshalling platform.
It conditions and digitizes one RTD temperature input in the CHARM I/O architecture. This role connects the RTD Input CHARM to the surrounding DeltaV Electronic Marshalling architecture.
Before commissioning, select the correct RTD type and wiring method; use a compatible CHARM terminal block; and verify sensor range and lead compensation in configuration.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Emerson KL3031X1-BA1:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Connects compatible RTD temperature sensors to a DeltaV Electronic Marshalling installation.
- Supports two-wire, three-wire, and four-wire RTD field configurations for the selected sensor type.
- Provides single-channel temperature acquisition for monitoring, control, and related process strategies.
- Uses a 24-bit analog-to-digital converter to provide high-resolution RTD temperature measurement.
- Maintains measurement repeatability within 0.05% of the configured operating span.
- Provides 90 dB typical common-mode rejection at DC and at both 50 Hz and 60 Hz.
- Requires no field calibration before the hardware is placed into its configured RTD service.
- Uses 0.5 mA excitation for 2- and 4-wire inputs and 0.25 mA for 3-wire RTD inputs.
- Set the correct sensor range and lead-wire compensation in the channel configuration before use.
- Matches the SE4303T03 RTD Input CHARM ordering identity used for the complete channel assembly.
- Supports the selected RTD element only when its required lead-wire method is configured correctly.
- Requires a terminal block designed for use with the corresponding DeltaV RTD Input CHARM.