Emerson VE4002S1T2B1 is an eight-channel DeltaV M-series 24 V DC high-side discrete output assembly.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for VE4002S1T2B1
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for VE4002S1T2B1

  • Manufacturer:
    Emerson
  • Part Number:
    VE4002S1T2B1
  • Product Family:
    DeltaV
  • Product Type:
    8-Channel 24 V DC High-Side Discrete Output Assembly
  • Stock:
    1
  • Termination:
    Standard I/O termination block
  • Number of channels:
    8
  • Output voltage range:
    2–60 V DC
  • Output current:
    1.0 A continuous per channel; 3.0 A maximum per I/O interface
  • Off-state leakage:
    1.2 mA maximum
  • Isolation:
    Optically isolated from the system; 1500 V DC factory test
  • LocalBus current:
    100 mA typical; 150 mA maximum at 12 V DC
  • Field circuit:
    3.0 A at 24 V DC per I/O interface
  • Output modes:
    Discrete output; momentary output; continuous pulse output
  • Momentary duration:
    100 ms–100 s
  • Continuous-pulse base:
    100 ms–100 s with 5 ms resolution
  • Optional terminal-block fuse:
    2.0 A
  • Tariff Code:
    8538900000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Modes Leakage Isolation Application
  • The complete order code includes the high-side output card and standard I/O termination block
  • Eight channels support discrete, momentary, and continuous-pulse output modes
  • Optical system isolation is built into the documented output architecture

VE4002S1T2B1 is an Emerson high-side discrete output assembly designed for the DeltaV M-series Traditional I/O platform.

It switches eight DC field loads and supports the documented momentary and pulse-output functions through the standard termination arrangement.

Before installation or replacement, verify the complete order code, carrier and terminal block, field voltage, per-channel and total load, output mode, protection, and saved DeltaV configuration.

Availability, condition, price, and shipping time for VE4002S1T2B1 are confirmed during quotation.

Emerson VE4002S1T2B1 8-Channel 24 V DC High-Side Discrete Output Assembly Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Channels can be configured for standard discrete output service
  • Momentary output duration is adjustable from 100 ms to 100 s
  • Continuous-pulse timing uses a 100 ms–100 s base with 5 ms resolution
  • Maximum off-state leakage is 1.2 mA
  • Load-state verification must account for the documented leakage current
  • Field devices must be compatible with the high-side switching arrangement
  • The output circuitry is optically isolated from the DeltaV system
  • The documented isolation boundary is factory tested at 1500 V DC
  • Field-circuit power is separate from the 12 V DC LocalBus supply
  • 24 V DC solenoid and relay control in DeltaV process systems
  • Momentary actuator commands using configured output duration
  • Continuous pulse outputs for compatible low-frequency field loads
Description
VE4002S1T2B1 is an Emerson eight-channel 24 V DC high-side discrete output assembly for the DeltaV M-series Traditional I/O platform.

The assembly switches 2–60 V DC loads at up to 1.0 A continuously per channel, subject to the documented 3.0 A maximum for the I/O interface, and supports discrete, momentary, and pulse modes.

Before installation or replacement, confirm the complete order code, carrier and termination, field voltage, load current, output mode, protection, wiring polarity, and saved configuration.
Alternative Names
VE4002S1T2B1 VE4002 S1T2B1 Emerson VE4002S1T2B1 DeltaV VE4002S1T2B1 Emerson DeltaV VE4002S1T2B1 VE4002S1 T2B1
Technical notes
VE4002S1T2B1 requires the standard termination, field voltage, individual and total load current, output mode, protective device, wiring polarity, and saved DeltaV configuration to be verified before commissioning.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can Emerson VE4002S1T2B1 supply 1.0 A on every channel simultaneously?
Each channel is rated 1.0 A continuous, but the complete I/O interface is limited to 3.0 A maximum; total loading must be calculated.
Which output modes are available on Emerson VE4002S1T2B1?
DeltaV documents discrete, momentary, and continuous-pulse output modes for this high-side output assembly.
What is the off-state leakage of Emerson VE4002S1T2B1?
The published maximum off-state leakage is 1.2 mA, which must be considered for sensitive field loads.
What voltage loads can Emerson VE4002S1T2B1 switch?
The documented output voltage range is 2–60 V DC; verify the actual field voltage and load current before use.
Is Emerson VE4002S1T2B1 isolated from the DeltaV system?
Yes. The output circuitry is optically isolated from the system and factory tested at 1500 V DC.
Can Emerson VE4002S1T2B1 be used with the fused I/O termination configuration?
VE4002S1T2B1 is the standard I/O termination configuration. Emerson lists VE4002S1T2B2 as the fused I/O termination configuration, so the complete order code and terminal hardware must be matched before replacement.
What should be checked before replacing Emerson VE4002S1T2B1?
Confirm the order code, termination hardware, field voltage, total load, output-mode settings, wiring polarity, protection, and saved DeltaV configuration.