Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power provides quotations, technical documentation and configuration support for this DeltaV output card.

KJ3001X1-BH1 12P0558X152

/ 4.9
1001 reviews | Need a Specific Revision?
Emerson KJ3001X1-BH1 12P0558X152 is a DeltaV M-series eight-channel isolated AC discrete-output card for 120/230 VAC field circuits.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for KJ3001X1-BH1 12P0558X152
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for KJ3001X1-BH1 12P0558X152

  • Manufacturer:
    Emerson
  • Part Number:
    KJ3001X1-BH1 12P0558X152
  • Product Family:
    DeltaV
  • Product Type:
    DeltaV M-series 8-Channel 120/230 VAC Isolated Discrete Output Card
  • Stock:
    1
  • Emerson part number:
    12P0558X152
  • Card type:
    8-channel 120/230 VAC isolated discrete output
  • Number of channels:
    8
  • Output range:
    20–250 VAC
  • Output rating:
    1 A continuous per channel
  • Combined output:
    2 A max up to 60°C; 3 A max up to 50°C
  • Isolation:
    250 VAC optical isolation from system and between channels
  • Off-state leakage:
    2 mA max at 120 VAC; 4 mA max at 230 VAC
  • LocalBus current:
    100 mA typical; 150 mA max at 12 VDC nominal
  • Field-circuit power:
    None
  • Output modes:
    Discrete; momentary; continuous pulse
  • Timing range:
    100 ms–100 s; 5 ms continuous-pulse resolution
  • Terminal-block keying:
    F4
  • Terminal-block options:
    Standard I/O or fused terminal block
  • Optional fuse:
    2 A
  • Weight:
    0.22 kg
  • Estimated shipping dimensions:
    4.1 x 12.5 x 10.4 cm
  • Tariff Code:
    Please confirm the destination before shipping
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Output Modes Isolation & Power Terminal Interface Product Applications

Features:

  • Eight isolated AC outputs: Each channel is separated from the DeltaV system and from the other output channels at 250 VAC.
  • Three output behaviors: Discrete, momentary and continuous-pulse modes support steady, timed and repeating control actions.
  • F4 terminal interface: The card is paired with standard or fused F4-keyed terminal-block options in M-series Traditional I/O.
AC output role: KJ3001X1-BH1 12P0558X152 switches 20–250 VAC field circuits across eight channels while keeping the channel paths electrically separated.

Load planning: The per-channel rating and total card limit work together, so enclosure temperature and simultaneous demand both shape the usable load plan.

DeltaV integration: The card combines its F4-keyed termination, LocalBus electronics and selectable output behavior within the M-series Traditional I/O architecture.

Apter Power supports Emerson KJ3001X1-BH1 12P0558X152 DeltaV M-series 8-Channel 120/230 VAC Isolated Discrete Output Card sourcing with quotations, technical documentation and configuration review.
Emerson KJ3001X1-BH1 12P0558X152 DeltaV M-series 8-Channel 120/230 VAC Isolated Discrete Output Card Manuals,Datasheets,Link
Important Notice: These links support product identification and service planning for KJ3001X1-BH1 12P0558X152. Apter Power can help match the card, terminal-block key and installed DeltaV configuration.
  • Discrete output: The channel holds the last state submitted by the controller.
  • Momentary output: A channel remains active for a configured interval from 100 ms to 100 s.
  • Continuous pulse: The output repeats as a percentage of a configured 100 ms to 100 s base period.
  • Pulse resolution: Continuous-pulse timing is adjustable in 5 ms steps.
  • System isolation: Each output channel is optically isolated from the DeltaV system at 250 VAC.
  • Channel separation: The eight outputs are also isolated from one another at 250 VAC.
  • Field supply: The card provides no field-circuit power, so the switched load uses an external AC source.
  • LocalBus demand: Electronics draw 100 mA typical and 150 mA maximum at 12 VDC nominal.
  • Function key: Emerson assigns F4 keying to the eight-channel 120/230 VAC isolated output card.
  • Standard termination: The regular eight-channel I/O terminal block is listed for this card type.
  • Fused termination: A fused terminal block is also listed, with an optional 2 A fuse.
  • M-series hardware: Traditional I/O uses MQ, MX or PK controllers with M-series horizontal or VerticalPlus carriers.
  • Steady AC switching: Discrete mode suits process outputs that remain in the controller-commanded state.
  • Timed actuation: Momentary mode supports a single defined active interval without changing the card hardware.
  • Repeating duty cycles: Continuous-pulse mode supports periodic ON/OFF behavior using a configured base period.
  • Isolated AC channels: Channel-to-channel isolation separates the eight output paths, while the installed wiring and protection must still follow the approved field-circuit design.
Description
Within a DeltaV M-series carrier, KJ3001X1-BH1 12P0558X152 keeps every AC switching path optically separated from both the system electronics and its neighboring channels. This architecture gives cabinet designers one card for several independent field circuits while retaining the electrical separation built into the output type.

When the control sequence needs more than a maintained state, KJ3001X1-BH1 12P0558X152 can deliver a single timed actuation or a repeating pulse pattern as well as conventional discrete switching. The application engineer can therefore select the required behavior in DeltaV without changing to a different output-card type.

Terminal planning is defined by F4 keying and the choice of standard or fused terminal-block arrangements. Specifying KJ3001X1-BH1 12P0558X152 together with the required terminal option gives procurement and maintenance teams a clearer DeltaV I/O bill of materials.
Alternative Names
KJ3001X1 BH1 KJ3001X1BH1 12P0558X152 KJ3001X1-BH1-12P0558X152
Technical notes
The 1 A per-channel rating for KJ3001X1-BH1 12P0558X152 is not an 8 A card allowance. Emerson limits the combined output to 2 A up to 60°C or 3 A up to 50°C. Apter Power can help align the spare with the enclosure temperature and simultaneous-load plan.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
A low-current indicator stays faintly lit after the KJ3001X1-BH1 12P0558X152 output turns OFF. Does that mean the card has failed?
Not necessarily. Emerson specifies maximum off-state leakage of 2 mA at 120 VAC and 4 mA at 230 VAC for this output type. Compare those values with the indicator's off-state threshold before attributing the faint light to the module.
Can KJ3001X1-BH1 12P0558X152 deliver one 200 ms actuation without adding a separate timing relay?
Yes. The documented momentary-output mode covers a 200 ms interval within its 100 ms to 100 s range. The DeltaV channel can apply that configured active time when the process sequence calls for one timed action.
Which output mode should be used when KJ3001X1-BH1 12P0558X152 must repeat an ON/OFF duty cycle?
Continuous-pulse mode is the documented choice for a repeating duty cycle. It uses a configured 100 ms to 100 s base period with 5 ms resolution, while momentary mode produces one timed active interval.
Does KJ3001X1-BH1 12P0558X152 supply the AC power required by the field load?
No field-circuit power is provided by the card. It switches the external AC circuit, so the load design needs its own suitable supply within the published 20–250 VAC output range.
What does the channel-to-channel isolation of KJ3001X1-BH1 12P0558X152 mean for a field-circuit review?
Emerson specifies 250 VAC optical isolation from the DeltaV system and between individual channels. This identifies the isolated output type, but it does not by itself authorize mixing supplies; verify the installed wiring, protection and applicable rules separately.
Which terminal-block key should match KJ3001X1-BH1 12P0558X152 in an M-series carrier?
Emerson assigns F4 keying to the eight-channel 120/230 VAC isolated output card and lists both standard and fused terminal-block options. Matching that function key helps preserve the intended card-to-terminal interface.