Features:
- Supports sixteen source-type I/O circuits for 24 VDC two-wire, three-wire, and electromechanical sensors.
- Lets each circuit serve as an input, tristate input, or protected 2 A output.
- Uses 18-30 VDC control power with configurable filtering and comprehensive point diagnostics.
The 24 VDC version accepts 18-30 VDC and uses a 1.8 kΩ typical input impedance for its source-type points.
Combined output current is limited to 15 A at 35°C, even though each circuit is rated for 2 A steady state.
Selectable input filtering, pulse testing, output defaults, and redundancy settings allow point behavior to be tailored without external logic.
Apter Power may retain purchase and support options for the General Electric IC660BBD022 24 VDC 16 Circuit Source I/O Block after manufacturer EOL.
General Electric IC660BBD022 24 VDC 16 Circuit Source I/O Block Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC660BBD022 24 VDC 16 Circuit Source I/O Block Specs
General
- ManufacturerGeneral Electric
- ModelIC660BBD022
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
24 VDC Field Connections
- Two-wire Sensors: Supports compatible two-wire solid-state sensors.
- Three-wire Sensors: Accepts three-wire solid-state devices.
- Contacts: Works with electromechanical sensors and dry contacts.
- Tristate Resistor: Uses a 1.6 kΩ external resistor for open-wire supervision.
Point Configuration
- Input Mode: Reads a 24 VDC source-type input.
- Tristate Mode: Adds electrical open-wire detection.
- Output Mode: Drives loads at up to 2 A per circuit.
- Power Source: Draws block power from the connected I/O supply.
- Defaults: Output power-up and communications-loss behavior are configurable.
Protected Output Operation
- Inrush Protection: Shuts down if surge current exceeds the protection threshold.
- Overload: Reports sustained output overload.
- No Load: Detects insufficient current on an enabled output.
- Failed Switch: Identifies a switching fault.
- Recovery: Allows output restoration by controller or hand-held monitor command.