Features:
- Executes local programmable logic inside a Field Control station
- Provides 6K words of application memory and 2K words of registers
- Receives its 6.5 VDC supply directly from the Field Control backplane
IC670MFP100 is a specialized Micro PLC rather than a passive I/O module. It runs the local application and exchanges discrete, analog, register, Genius global-data, and fault information with the station Bus Interface Unit.
The documented physical envelope is 3.25 by 2.0 by 2.9 inches, with a weight of 0.35 pound. Typical Boolean execution is 1.0 millisecond per K of logic, which should be considered together with the configured I/O sweep.
Programming can be performed with the supported Logicmaster 90-30/20/Micro package or a compatible Series 90 hand-held programmer. Application and configuration backups should be verified before any processor exchange.
Apter Power can review program backup, memory use, and station compatibility for the General Electric IC670MFP100 Series 90 Micro Field Processor.
General Electric IC670MFP100 Series 90 Micro Field Processor Manuals, Datasheets, Links
General Electric IC670MFP100 Series 90 Micro Field Processor Specs
General
- ManufacturerGeneral Electric
- ModelIC670MFP100
- ConditionNew Original ready stock
- Product FamilyField Control Distributed I/O
Memory and execution resources
- Program memory: Stores up to 6K words of the IC670MFP100 user application.
- Registers: Provides 2K words of register memory for logic and data handling.
- Analog references: Supports 128 analog input words and 128 analog output words.
- Scan performance: Typical Boolean execution is 1.0 ms per K of logic.
Application maintenance
- Software: Use the documented Logicmaster 90-30/20/Micro programming environment.
- Hand-held option: A compatible Series 90 hand-held programmer is also supported.
- Backup: Save the complete program, configuration, and reference allocation before service.
- Fault review: Read and preserve the processor fault table before clearing or replacing the unit.
Processor replacement checks
- Station capacity: A station containing IC670MFP100 supports the processor plus the documented number of I/O modules.
- Backplane power: Confirm the 6.5 VDC backplane source; no separate field-power lead is required.
- Physical fit: Allow for the 3.25 x 2.0 x 2.9 inch module envelope.
- Startup: Restore the approved program, verify mode and sweep operation, then test local and network I/O.