Features:
- Electronic protection applied independently to each output
- Separate green state and yellow fault indicators
- Fault information returned through the Field Control station
Rather than protecting the whole group with one common fuse,
IC670MDL730 monitors the current condition of each sourcing output and isolates the channel that encounters an overload.
The paired indicator scheme supports maintenance at the module face: a green LED follows the commanded state, and a yellow LED draws attention to a point-level fault.
When matching a replacement to an installed station, the Bus Interface Unit revision and the steady-state and inrush demand of every connected load must remain inside the documented limits.
The General Electric IC670MDL730 24 VDC Positive Logic ESCP Discrete Output Module may remain available for quotation and legacy-system support through Apter Power.
General Electric IC670MDL730 24 VDC Positive Logic ESCP Discrete Output Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC670MDL730 24 VDC Positive Logic ESCP Discrete Output Module Specs
General
- ManufacturerGeneral Electric
- ModelIC670MDL730
- ConditionNew Original ready stock
- Product FamilyField Control Distributed I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Electronic Safeguards
- Point protection: Each output includes electronic overcurrent and short-circuit protection.
- Recovery: Remove the overload and follow the documented reset behavior before returning the point to service.
- Module limit: Combined load current must remain within the 8 A module rating.
- Supply window: The user supply must stay between 18 and 30 VDC.
Status and Fault Indication
- Green LEDs: A green indicator shows the commanded state of each output.
- Yellow LEDs: A yellow indicator identifies a detected point fault.
- Controller data: Fault information is reported through the Field Control station.
- Troubleshooting: Inspect load wiring and current demand before replacing the module.
BIU and Load Checks
- Genius BIU: IC670GBI002 requires revision 2.10 or later.
- Other BIUs: Profibus and Interbus-S BIUs require revision 1.0 or later.
- Load matching: Evaluate steady-state and inrush current for every connected device.
- Terminal wiring: Use the official terminal assignment and common-connection diagrams.