Features:
- Arranges eight 120 VAC outputs as four independently isolated two-point groups.
- Delivers up to 2 A per output for higher-current AC loads.
- Protects every point with a 3 A slow-blow fuse and snubber while supporting 20 A one-cycle inrush.
IC670MDL331 arranges eight 120 VAC outputs as four isolated pairs so each two-point group can use an independent field reference.
Every output carries a 2 A rating and includes its own 3 A, 250 V slow-blow fuse plus a snubber network.
The 20 A one-cycle inrush capability supports demanding AC loads when group current and temperature-dependent module limits are respected.
Manufacturer End-of-Life (EOL) does not necessarily end availability: Apter Power may still offer the General Electric IC670MDL331 120 VAC Isolated 2 A Discrete Output Module for purchase and support.
General Electric IC670MDL331 120 VAC Isolated 2 A Discrete Output Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC670MDL331 120 VAC Isolated 2 A Discrete Output Module Specs
General
- ManufacturerGeneral Electric
- ModelIC670MDL331
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Four Isolated Output Pairs:
- Output capacity: 8 AC output points
- Group arrangement: Four isolated groups with 2 outputs per group
- Load range: 85–132 VAC at 47–63 Hz
- Point current: 2 A maximum per output
Current and Inrush Limits:
- Group current: 2 A maximum per isolated pair
- Module current: 6–8 A depending on ambient temperature
- Inrush capability: 20 A for one AC cycle
- Thermal loading: Total usable current follows the documented temperature derating
Protected AC Output Paths:
- Point fuse: 3 A, 250 V slow-blow fuse on each output
- Snubber network: Each output includes transient suppression
- BIU current: 154 mA maximum
- System interface: Field Control Bus Interface Unit