Features:
- Three isolated input groups with two RTD circuits each
- Internal calibration references used during channel scanning
- Temperature, resistance, or count reporting modes
The isolated grouping in
IC660BBA021 separates pairs of sensors while one block handles all six measurement circuits on the Genius bus.
During acquisition, the multiplexer includes internal reference resistors in the scan so that channel conversion can be checked against known values.
The selected update period determines the available measurement resolution, allowing a configuration to favor faster reporting or finer conversion detail.
The General Electric IC660BBA021 Genius Analog Input Block is available for quotation, documentation, and system-matching support through Apter Power.
General Electric IC660BBA021 Genius Analog Input Block Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC660BBA021 Genius Analog Input Block Specs
General
- ManufacturerGeneral Electric
- ModelIC660BBA021
- ConditionNew Original ready stock
- Product FamilyGenius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Sensor and Wiring Options
- Platinum: DIN 43760 platinum RTDs are supported.
- Nickel: DIN 43760 nickel RTDs may be selected.
- Copper: The block includes a copper RTD measurement mode.
- Lead wiring: Two-wire and three-wire connections are documented for field sensors.
Measurement Processing
- Resolution: Temperature data is resolved to 0.1 degree C.
- Update choices: Select a 400, 800, or 1600 ms update period.
- Linearization: Input values are linearized for the configured RTD characteristic.
- Calibration: The block is factory-calibrated and does not require routine recalibration.
Sensor Fault Identification
- Open wire: The diagnostic identifies missing sensors or interrupted leads.
- Wiring error: Incorrect terminal connections can be distinguished from a valid measurement.
- Input short: Measurements below the expected RTD range can generate a shorted-input fault.
- Alarms: High, low, overrange, and underrange indications support process monitoring.