Features:
- Integrates a 12.1-inch SVGA touch display with an industrial PC platform.
- Provides dual Ethernet, three serial ports and two USB connections.
- Protects the installed front panel to NEMA 4 and IP65 levels.
IC5002CAC0000 presents machine information through a 307.4 mm color screen with 800 x 600 resolution.
Front keys give IC5002CAC0000 direct access to the soft keyboard, task selection and display adjustment functions.
Hardware status monitoring on IC5002CAC0000 covers fan operation and excessive internal temperature.
The touchscreen controller on the General Electric IC5002CAC0000 Intelligence PanelClient occupies internal COM4, leaving COM1, COM2 and COM3 available as external RS-232 service connections.
General Electric IC5002CAC0000 Intelligence PanelClient Manuals,Datasheets,Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Local Workflow
- Soft Keyboard: A front key opens the on-screen keyboard for local text entry.
- Task Selection: The task control moves between active Windows applications.
- Display Adjustment: Dedicated controls raise or lower the backlight setting.
- Context Commands: A right-mouse function supports software commands at the panel.
Service Connections
- Network Setup: Each Ethernet interface requires the addressing and driver configuration used by the plant network.
- Serial Assignment: COM4 remains dedicated to the touchscreen, leaving COM1 through COM3 for external devices.
- External Display: A compatible multisync monitor can operate with the integrated screen.
- Safe Handling: Peripheral leads should be attached or removed only while the panel computer is switched off.
Mounting Process
- Cabinet Opening: Prepare a 318 x 256 mm recess with the stated +1.0 mm allowance.
- Rear Access: Reserve 177 mm of mounting depth behind the panel surface.
- Air Space: Maintain 50 mm above and below and 30 mm at both sides.
- Clamp Load: Tighten the mounting screws evenly without exceeding 0.25 N-m.
Status Response
- Processor Fan: Monitoring variables identify a slow or stopped CPU fan.
- Chassis Cooling: The enclosure fan condition is available to compatible software.
- Temperature Alarm: Internal temperature above 50 degrees C produces an overheat indication.
- Front LED: Green, red and flashing-red states distinguish ready, fan-fault and heat conditions.