Features:
- Places the I/O Link Remote role in the distant Series Three base unit.
- Exchanges rack data with a matching I/O Link Local module over twisted-pair wiring.
- Supports documented remote-point selections of 8, 16, 32, or 64.
IC630CCM311 terminates the remote side of the Series Three link, while the corresponding local module remains with the controller-side rack.
The RS-422-compatible channel may extend to 3300 ft (1 km), allowing the remote base unit to be positioned near its field wiring while retaining the planned point assignment.
Remote-rack loading must include 800 mA at +5 VDC for IC630CCM311, and the base unit must be dedicated to either input or output service.
Apter Power can assist with availability and relevant documentation for the General Electric IC630CCM311 I/O Link Remote Module.
General Electric IC630CCM311 I/O Link Remote Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Remote-link position
- Rack side: IC630CCM311 is installed at the distant Series Three base unit.
- Paired device: The controller-side rack uses an I/O Link Local module.
- Data path: I/O information is exchanged between the local and remote roles.
- System use: The remote group can participate in a larger Series Five arrangement through the Series Three interface structure.
Remote-channel wiring
- Interface: The link associated with IC630CCM311 is RS-422 compatible.
- Medium: Physical connection is made with twisted-pair cable.
- Distance: The remote base unit may be located up to 3300 ft (1 km) from the first base unit.
- Commissioning check: Cable order, continuity, route condition, and end-to-end length should match the recorded installation.
Remote-point arrangement
- Point choices: IC630CCM311 supports 8, 16, 32, or 64 transmitted remote points.
- Excluded setting: A 48-point selection is not allowed.
- Base-unit role: A remote base is assigned to inputs or to outputs.
- Slot rule: Input and output circuits are not mixed in one remote-I/O slot.
Rack-load allowance
- Load units: The Series Three table assigns IC630CCM311 80 units on the +5 VDC rail.
- Unit value: One load unit equals 10 mA.
- Calculated demand: The module contributes 800 mA to the worst-case +5 VDC total.
- Other rail: No +12 VDC load is listed for IC630CCM311.