Features:
- Combines thirty-two 24 VDC sink inputs in one Series Three module.
- Provides local LED indication for the individual field states.
- Uses a D-style connector for the high-density field interface.
IC630MDL306 concentrates a full block of low-voltage discrete inputs in one rack position, supporting cabinets that already organize their field signals around a single 32-point module.
Individual front indications let operators compare physical input activity with the controller state without disconnecting the field interface.
The connector-based arrangement keeps the dense signal group at one module boundary while preserving the established Series Three rack structure.
Apter Power can support quotation and documentation requests for the General Electric IC630MDL306 24 VDC Sink Input Module.
General Electric IC630MDL306 24 VDC Sink Input Module Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Dual-cable field connection
- Cable set: IC630MDL306 uses two interface cables for its high-density field connections.
- Rack end: Each ten-foot cable has a 40-pin female connector that mates with the module faceplate.
- Field end: The opposite conductors are tinned for connection to user devices.
- Wire tracking: Each conductor is color coded to simplify point identification.
Input-state diagnostic path
- State comparison: Compare the programmer state with the corresponding IC630MDL306 LED.
- Matched state: When state and LED agree, inspect the field device and measure voltage at the input.
- State mismatch: If the signal reaches the input but the programmer disagrees, the module becomes the replacement candidate.
- Common fault: If several input modules appear faulty, examine the shared I/O cable and connector first.
Backplane load allocation
- Five-volt allocation: IC630MDL306 uses eight +5 V load units.
- Current equivalent: Ten milliamperes per unit produces an 80 mA rack allowance.
- Twelve-volt rail: The module adds no +12 V load.
- Calculation case: The allocation assumes all thirty-two inputs are energized.
Slot-based point assignment
- Slot origin: The base-unit position establishes the first reference for IC630MDL306.
- Point count: The CPU recognizes the module as a thirty-two-point input.
- Reference block: All points receive consecutive addresses from the slot starting reference.