Technical specifications for IC630MDL368

  • Manufacturer:
    General Electric
  • Part Number:
    IC630MDL368
  • Product Family:
    GE Intelligent Platforms
  • Product Type:
    Series Three 2-Channel Voltage/Current Analog Output Module
  • Stock:
    1
  • Output Channels:
    2
  • Voltage Output Range:
    0-10 VDC
  • Current Output Range:
    4-20 mA
  • 5 VDC Backplane Load:
    33 units (330 mA)
  • 12 VDC Backplane Load:
    None listed
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Output Modes Channel Layout Power Budget Range Choice

Features:

  • Combines two analog command circuits in one Series Three module.
  • Supports either 0-10 VDC receivers or 4-20 mA current loops.
  • Places a 33-unit demand on the rack 5 VDC supply.
General Electric IC630MDL368 serves unipolar voltage and current-command interfaces without changing the two-channel module footprint.

Channel wiring should be planned around the destination type because voltage and current receivers use different field-loop arrangements.

The 33-unit assignment equals 330 mA at 5 VDC and must be counted with every other load in the Series Three rack.

The General Electric IC630MDL368 Series Three 2-Channel Voltage/Current Analog Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IC630MDL368 Series Three 2-Channel Voltage/Current Analog Output Module Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Voltage and Current Modes

  • Voltage Mode: The published unipolar voltage span is 0-10 VDC.
  • Current Mode: The alternative current-loop span is 4-20 mA.
  • Destination Match: Each receiving device must support the format selected for its channel.
  • Negative Commands: The listed voltage option does not extend below 0 V.

Two-Channel Arrangement

  • Channel Quantity: Two analog outputs are available from one module position.
  • Separate Loads: Each output can feed its own compatible field interface.
  • Format Planning: Voltage and current destinations require the corresponding circuit arrangement.
  • Loop Verification: Continuity and return paths should be checked before a current loop is commissioned.

Backplane Allocation

  • Assigned Units: The Series Three table assigns 33 load units at 5 VDC.
  • Converted Demand: That assignment represents 330 mA of 5 VDC rack current.
  • Additional Rail: No 12 VDC load is shown for this analog output configuration.
  • Expansion Review: The new demand must be added to the existing rack total before expansion.

Neighboring Analog Options

  • IC630MDL366A: Uses two 1-5 VDC or 4-20 mA analog output circuits.
  • IC630MDL367A: Uses two -10 to +10 VDC bipolar output circuits.
  • IC630MDL368A: Uses two 0-10 VDC or 4-20 mA output circuits.
  • Interface Decision: The receiver range determines which neighboring Series Three variant fits.
Description
Designed for Series Three systems that need either voltage or current commands, General Electric IC630MDL368 is a two-channel analog output module supporting 0-10 VDC and 4-20 mA interfaces. It allows one module type to serve compatible receivers built around either signal format.

The two outputs share a single rack position and place a 330 mA load on the 5 VDC backplane supply, with no listed demand on the 12 VDC rail.

At the field connection, each output must use the format expected by its destination: 0-10 VDC for a voltage input or 4-20 mA for a current loop. Matching the signal type prevents incorrect scaling or an unresponsive receiver.
Revisions

Revision Part #

Also known as

IC630MDL368A
IC630MDL368-A, Series A, Rev A
Alternative Names
IC630-MDL368 IC630 MDL368 IC 630 MDL 368 GE IC630MDL368 GE Fanuc IC630MDL368 IC630MDL368A IC630MDL368-A IC63OMDL368
Technical notes
Each General Electric IC630MDL368 channel must use one compatible field format at its destination. The Series Three 5 VDC supply must reserve 330 mA for the module.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which receiver types can be paired with General Electric IC630MDL368?
General Electric IC630MDL368 can be matched to compatible 0-10 VDC inputs or 4-20 mA receiving loops.
Why could a 4-20 mA loop connected to General Electric IC630MDL368 fail to respond?
Verify loop continuity, return wiring, and current-mode selection because General Electric IC630MDL368 must be configured and connected for the same signal format.
How many separate commands can General Electric IC630MDL368 provide?
Two analog output circuits are available on General Electric IC630MDL368 for two compatible destinations.
What should be included in the power calculation for General Electric IC630MDL368?
Add 330 mA to the Series Three 5 VDC rack total when General Electric IC630MDL368 is installed.
Can General Electric IC630MDL368 directly provide a negative voltage command?
No; General Electric IC630MDL368 is published for 0-10 VDC or 4-20 mA, not a negative-to-positive bipolar voltage span.

Product Browsing History