Features:
- Combines two analog command circuits in one Series Three module.
- Supports either 0-10 VDC receivers or 4-20 mA current loops.
- Places a 33-unit demand on the rack 5 VDC supply.
General Electric IC630MDL368 serves unipolar voltage and current-command interfaces without changing the two-channel module footprint.
Channel wiring should be planned around the destination type because voltage and current receivers use different field-loop arrangements.
The 33-unit assignment equals 330 mA at 5 VDC and must be counted with every other load in the Series Three rack.
The General Electric IC630MDL368 Series Three 2-Channel Voltage/Current Analog Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IC630MDL368 Series Three 2-Channel Voltage/Current Analog Output Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Voltage and Current Modes
- Voltage Mode: The published unipolar voltage span is 0-10 VDC.
- Current Mode: The alternative current-loop span is 4-20 mA.
- Destination Match: Each receiving device must support the format selected for its channel.
- Negative Commands: The listed voltage option does not extend below 0 V.
Two-Channel Arrangement
- Channel Quantity: Two analog outputs are available from one module position.
- Separate Loads: Each output can feed its own compatible field interface.
- Format Planning: Voltage and current destinations require the corresponding circuit arrangement.
- Loop Verification: Continuity and return paths should be checked before a current loop is commissioned.
Backplane Allocation
- Assigned Units: The Series Three table assigns 33 load units at 5 VDC.
- Converted Demand: That assignment represents 330 mA of 5 VDC rack current.
- Additional Rail: No 12 VDC load is shown for this analog output configuration.
- Expansion Review: The new demand must be added to the existing rack total before expansion.
Neighboring Analog Options
- IC630MDL366A: Uses two 1-5 VDC or 4-20 mA analog output circuits.
- IC630MDL367A: Uses two -10 to +10 VDC bipolar output circuits.
- IC630MDL368A: Uses two 0-10 VDC or 4-20 mA output circuits.
- Interface Decision: The receiver range determines which neighboring Series Three variant fits.