The H2 input circuits are intended for a nominal 24 V DC floating wetting supply. The connected PDIO reads board identification and feedback data so the control system can identify incompatible hardware and field-side faults.
IS200TDBSH2A is the 24 V DC simplex member of the TDBS family and accepts a single PDIO pack with one or two Ethernet paths to the controllers. It is not the TMR TDBT arrangement, and H4/H6 boards use different contact-wetting ranges.
Relay functions may be extended with WROB, WROF, or WROG option boards. Each option changes power distribution, fuse placement, and feedback behavior, so the installed option-board identity and wiring drawing must be retained during replacement.
The PDIO monitors contact-input wetting voltage, reads each input state, and receives relay-position feedback from isolated contact pairs. Sequence-of-events reporting can be enabled for individual input transitions and relay commands.
When a WROB, WROF, or WROG option board is installed, fuse-status feedback is also processed according to that board’s circuit arrangement. Service analysis should therefore separate contact excitation, relay command, relay feedback, and option-board fuse indications.
A loss of wetting voltage, a contact input that does not respond to the periodic high/low threshold test, or a mismatch between relay command and feedback can each raise a distinct diagnostic. The terminal-board ID device also reports board type, serial number, and revision to the I/O processor.
If multiple inputs fail together, verify the common wetting supply before replacing the board. For a single relay issue, compare the command, relay-position feedback, load condition, and any option-board fuse indication.
IS200TDBSH2A is used where a simplex PDIO path must combine field contact inputs and relay outputs on one terminal board. The manual documents nominal 24 V DC wetting for its contact-input section and permits optional relay arrangements for externally powered loads, individually fused relay commons, or fused common power distribution.
The board is suited to replacement in an established Mark VIe cabinet only after the installed PDIO pack, H2 wetting-voltage range, relay option board, terminal schedule, and mounting arrangement have been matched.