Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power can quote and source IC600PM541 and provide the applicable General Electric GEK-96602A manufacturer documentation.

IC600PM541

/ 4.9
1001 reviews | Need a Specific Revision?
General Electric IC600PM541 is a Series Six Plus 24 VDC CPU/DPU power supply that accepts 20–32 VDC and provides regulated +5, +12, and -12 VDC rack power.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for IC600PM541
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for IC600PM541

  • Manufacturer:
    General Electric
  • Part Number:
    IC600PM541
  • Product Family:
    GE Series Six Plus
  • Product Type:
    24 VDC CPU/DPU Power Supply Module
  • Stock:
    1
  • Rack use:
    Series Six Plus 19-inch CPU or DPU rack
  • Input voltage:
    20 to 32 VDC
  • Maximum input power:
    180 VA
  • Input fuse:
    8 A slow-blow
  • Polarity protection:
    Reverse-polarity protected
  • Allowable interruption:
    10 ms minimum at 20 VDC
  • +5 VDC output:
    16.5 A maximum
  • +12 VDC output:
    1.5 A maximum
  • -12 VDC output:
    1.0 A maximum
  • Total output power:
    Less than 90 W across all outputs
  • Rack load capacity:
    275 load units
  • Load-unit reference:
    Approximately 60 mA per unit
  • Auxiliary battery input:
    8 to 28 VDC with integrated regulator
  • Processor control:
    CPU RUN/STOP keyswitch
  • Memory control:
    MEMORY PROTECT/WRITE keyswitch
  • Alarm contacts:
    Two isolated NO/NC relay sets
  • Alarm contact load:
    Resistive, maximum 1 A at 115 VAC or 28 VDC
  • Normal alarm state:
    Relays energized
  • Power indicator:
    On when all three DC outputs are within tolerance
  • Rack location:
    Extreme right side of CPU/DPU rack
  • Operating temperature:
    0 to 60 degrees C
  • Storage temperature:
    -20 to 80 degrees C
  • Humidity:
    5 to 95% non-condensing
  • Estimated shipping dimensions:
    317 x 229 x 70 mm (12.46 x 9.00 x 2.75 in)
  • Tariff Code:
    8504409999
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals DC Source Rack Power Panel Controls Alarm Outputs

Features:

  • Battery and inverter sources can feed the processor rack across the 20-32 VDC input range.
  • A 275-unit power budget is divided among +5, +12, and -12 VDC backplane rails.
  • Isolated relay contacts provide an external indication when the supply leaves its normal state.
IC600PM541 powers a Series Six Plus 19-inch CPU or DPU rack directly from a nominal 24 VDC source instead of AC mains.

The supply combines reverse-polarity protection and an 8 A slow-blow fuse with the regulated outputs needed by processor modules.

Front key switches control CPU operation and memory writing, while separate alarm and auxiliary-backup connections support monitored installations.

Pricing enquiries for the General Electric IC600PM541 24 VDC CPU/DPU Power Supply can be handled by Apter Power with relevant GE manuals or product documentation.
General Electric IC600PM541 24 VDC CPU/DPU Power Supply Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Conditioning the processor-rack input

  • Operating window: IC600PM541 accepts direct-current sources between 20 and 32 VDC.
  • Source options: Station batteries and inverter outputs can feed the supply within that range.
  • Input fuse: An 8 A slow-blow element protects the incoming DC circuit.
  • Polarity defense: The front-end circuit limits damage from reversed source connections.

Supplying three processor backplane rails

  • Main logic rail: Up to 16.5 A is available from the regulated +5 VDC output.
  • Positive support rail: The +12 VDC output contributes as much as 1.5 A.
  • Negative support rail: A maximum of 1.0 A is supplied at -12 VDC.
  • Aggregate limit: Combined demand stays below 90 W and within 275 Series Six load units.

Managing CPU and memory states at the supply

  • Main disconnect: The faceplate switch and fuse isolate the DC-fed power assembly.
  • Processor key: CPU RUN/STOP selects whether the controller executes or halts its program.
  • Memory key: MEMORY PROTECT/WRITE governs permitted changes to stored controller logic.
  • Rail lamp: POWER indicates that the three regulated outputs remain within tolerance.

Connecting external supply supervision

  • Contact sets: Two electrically isolated relay groups each expose NO and NC terminals.
  • Healthy state: Both IC600PM541 alarm relays are energized during normal supply operation.
  • Contact rating: Each resistive circuit is limited to 1 A at 115 VAC or 28 VDC.
  • Backup input: An isolated 8-28 VDC auxiliary source can maintain the memory-support function.
Description
The General Electric IC600PM541 CPU/DPU Power Supply operates directly from a 20–32 VDC source such as a station battery or inverter and powers a Series Six Plus 19-inch processor rack.

Three regulated outputs let IC600PM541 deliver up to 16.5 A at +5 VDC, 1.5 A at +12 VDC, and 1.0 A at -12 VDC, with combined output power below 90 W and a 275-load-unit rack budget.

Front-panel hardware on IC600PM541 includes the main switch and fuse, CPU RUN/STOP and MEMORY PROTECT/WRITE key switches, plus a POWER indicator for the regulated rails.

Two isolated alarm-contact sets, reverse-polarity protection, and an auxiliary memory-backup input extend IC600PM541 for monitored DC-powered installations. The supply mounts at the extreme right of a CPU or DPU rack.
Alternative Names
IC600 PM541 IC600-PM541 IC-600-PM-541 GE IC600PM541 General Electric IC600PM541 Series Six Plus 24 VDC Supply IC600PM54I IC600PMS41
Technical notes
Keep the IC600PM541 auxiliary memory-backup circuit isolated from the rest of the system, and verify source polarity before energizing the 20–32 VDC input.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why can reversed DC wiring open the IC600PM541 input fuse?
IC600PM541 has reverse-polarity protection, but reversed input can draw enough current to open its 8 A slow-blow fuse.
What source drop can cause IC600PM541 rack power to collapse?
If the supply falls below the 20 VDC input range, IC600PM541 may no longer hold its regulated backplane outputs.
How should an IC600PM541 alarm contact be interpreted during operation?
IC600PM541 keeps its isolated alarm relays energized in the normal state, so a changed NO/NC state indicates a supply alarm.
Why must the IC600PM541 auxiliary backup circuit remain isolated?
An external common can short the IC600PM541 auxiliary battery path, so the backup source must stay isolated from other system circuits.
Which rack position accepts IC600PM541 in a Series Six Plus system?
IC600PM541 mounts at the extreme right of a 19-inch CPU or DPU rack and feeds the three regulated backplane rails.
How can IC600PM541 rack loading be checked before adding a module?
Total the module load units and keep the IC600PM541 rack within 275 units and the individual +5, +12, and -12 VDC limits.
What should be preserved before changing an IC600PM541 supply?
Record IC600PM541 input polarity, alarm and backup wiring, rack load, and the CPU and memory-key positions before isolating power.

Product Browsing History