Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power can assist with F2 DO 16 01 quotation requests and access to official HIMA technical files.

F2 DO 16 01

/ 4.9
1001 reviews | Need a Specific Revision?
HIMA F2 DO 16 01 is a HIMatrix safety-related remote output device with sixteen 24 VDC digital outputs and two integrated 100Base-TX SafeEthernet switch ports.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for F2 DO 16 01
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for F2 DO 16 01

  • Manufacturer:
    HIMA
  • Part Number:
    F2 DO 16 01
  • Product Family:
    HIMA HIMatrix system
  • Product Type:
    HIMatrix Remote I/O
  • Stock:
    1
  • Digital outputs:
    16 channels
  • Nominal output voltage:
    24 VDC
  • Ethernet switch ports:
    2 x 100Base-TX
  • Safety communication:
    SafeEthernet
  • Safety rating:
    SIL 3 / Category 4 / PL e
  • Rated supply range:
    20.4–28.8 VDC
  • Operating temperature:
    0 to 60 °C
  • Output supervision:
    Safety-related output diagnostics
  • Tariff Code:
    8537101190
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Output Use SafeEthernet Fault Response Applications

Features:

  • Sixteen safety-related outputs combine higher-current and standard-current load groups in one compact remote device.
  • Two integral 100Base-TX ports provide switched SafeEthernet connectivity without a separate adapter.
  • The output architecture is certified for SIL 3, Category 4 and PL e protective functions.
F2 DO 16 01 places actuator switching close to the controlled equipment while the central HIMatrix controller retains the safety application.

Its unequal output-current groups let one station serve field devices with different electrical demands when each circuit remains within the published load limits.

Channel and network diagnostics give maintenance teams separate indications for communication, supply and output-circuit conditions.

Apter Power can assist with quotation and official HIMA documentation access for HIMA F2 DO 16 01 HIMatrix safety-related remote output device.
HIMA F2 DO 16 01 HIMatrix safety-related remote output device Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

How F2 DO 16 01 Drives Field Loads

  • Load groups: Eight outputs support higher-current loads while the remaining eight serve lower-current circuits within the published limits.
  • Switching role: The channels energize safety-related actuators, interposing relays and shutdown devices from a remote cabinet location.
  • Safe state: A safety demand or diagnosed output fault causes the configured function to move the connected process toward its designed safe condition.
  • Field design: Each load circuit still requires its own verified supply, protection and terminal assignment.

Using F2 DO 16 01 on SafeEthernet

  • Integrated switch: Two Ethernet ports allow the device to sit directly in a HIMatrix safety network without an added communication adapter.
  • Safety data: Output commands and diagnostic states are exchanged through the certified SafeEthernet protocol.
  • Network path: The switched ports support a practical line topology between nearby HIMatrix devices.
  • Engineering basis: Addresses, cycle timing and safety parameters must match the approved controller project.

How F2 DO 16 01 Reports Output Problems

  • Channel supervision: Internal diagnostics help distinguish a commanded state from a channel or external-load problem.
  • Supply loss: A missing field supply can affect several outputs even when network communication remains available.
  • Short circuit: An overloaded or shorted load is isolated through the module diagnostic response rather than treated as a logic change.
  • Service sequence: Troubleshooting starts with the affected channel indication, field voltage and load wiring before hardware replacement.

Where F2 DO 16 01 Fits

  • Emergency shutdown: Remote outputs can operate shutdown solenoids close to process equipment while the safety logic remains in the controller.
  • Burner management: The mixed output-current capability suits ignition, trip and isolation devices with different load demands.
  • Machine safety: Distributed actuator circuits reduce long field runs in guarded-machine and packaged-skid layouts.
  • Cabinet layout: DIN-rail mounting combines I/O, communication and power connections in one compact remote assembly.
Description
HIMA F2 DO 16 01 is a HIMatrix safety-related remote output device that connects sixteen 24 VDC actuator circuits to a distributed safety controller.

Two integrated 100Base-TX switch ports let F2 DO 16 01 exchange safety data through SafeEthernet while remaining close to the controlled field equipment.

The certified output architecture of F2 DO 16 01 supports SIL 3, Category 4 and PL e applications when its channels, external loads and safe state are engineered within the approved limits.
Alternative Names
HIMA F2 DO 16 01 HIMatrix F2 DO 16 01 F2DO1601 F2-DO-16-01 F2 DO16 01 F2 DO 16-01 F2 D0 16 01 HIMA F2DO1601
Technical notes
F2 DO 16 01 operates from 20.4–28.8 VDC; its sixteen output circuits must remain within the certified load and environmental limits.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How should the field supply for F2 DO 16 01 be checked when an actuator remains off?
Begin at the assigned F2 DO 16 01 terminals: measure the field voltage, compare the connected load with its permitted rating, then read the channel diagnostic.
What network connection does F2 DO 16 01 use with a HIMatrix controller?
Communication between F2 DO 16 01 and the HIMatrix controller runs through its two integrated 100Base-TX ports using SafeEthernet.
Which output circuits are provided by F2 DO 16 01?
The output section of F2 DO 16 01 contains sixteen safety-related 24 VDC channels intended to switch controlled field loads.
What voltage range must be available to F2 DO 16 01?
A stable 20.4–28.8 VDC supply must be present at F2 DO 16 01 for operation within the certified electrical range.
How should a replacement F2 DO 16 01 be commissioned?
Once F2 DO 16 01 is installed, restore the approved SafeEthernet settings, exercise every assigned output and complete the required safety validation.
What should be checked when several F2 DO 16 01 outputs report faults together?
When several F2 DO 16 01 channels fault simultaneously, investigate the shared field supply, load grouping and terminal connections before suspecting the module.
Which safety application levels are supported by F2 DO 16 01?
Provided the complete protective function follows its certified design limits, F2 DO 16 01 can be applied up to SIL 3, Category 4 and PL e.