Features:
- 200 MHz 32-bit ARM9 processor with 32 MB SDRAM and 32 MB flash supports up to 128 I/O modules .
- 1oo1D and 1oo2D safety architectures with dual Ethernet, dual RS-232, and dual RS-485 for redundant communication .
- IEC 61508 SIL 3 certified; -25°C to +70°C operation with hot-swappable design and battery-backed real-time clock .
The T9300 is powered by a 32-bit ARM9 core processor running at 200 MHz, delivering the performance needed for complex safety logic execution in mid-sized to large AADvance systems . The module includes 32 MB of SDRAM for program execution and dynamic data storage, plus 32 MB of flash memory for non-volatile storage of the application program, configuration data, and firmware . This memory capacity allows the T9300 to handle large cause-and-effect matrices, complex mathematical functions, and extensive I/O configurations.
The T9300 supports multiple safety architectures to meet different availability and reliability requirements. In 1oo1D (one-out-of-one with diagnostics) configuration, a single T9300 processor module provides fail-safe operation suitable for SIL 2 applications where continuous process operation is not critical . In 1oo2D (one-out-of-two with diagnostics) configuration, two T9300 modules operate in parallel with diagnostics.
The T9300 is engineered for harsh industrial environments with an operating temperature range of -25°C to +70°C, making it suitable for outdoor installations, unheated control rooms, and extreme climate applications . The module includes a real-time clock with battery backup, which maintains accurate time stamps for sequence-of-events (SOE) logging even during power outages. For maintenance, the T9300 supports hot-swap replacement, allowing a faulty processor to be removed and replaced while the AADvance system remains powered and operational .
The T9300 ICS TRIPLEX I/O Base Unit may still be available for purchase and support from Apter Power beyond
End-Of-Life (EOL) by the manufacturer (OEM).
ICS TRIPLEX T9300 I/O Base Unit Manuals,
Datasheets, Drivers, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
ICS TRIPLEX T9300 I/O Base Unit Specs
General
- Manufacturer ICS TRIPLEX
- Model T9300
- Condition New Original ready stock
- Product Family
T9110,T9100,T8850C,T8830C
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
- Emergency Shutdown Systems (ESD): Deployed in petrochemical refining, deepwater offshore rigs, and chemical synthesis plants to execute millisecond-level safe-state trips if temperature or pressure limits are breached.
- Critical Process Control (PRC): Running within high-availability energy sectors (nuclear or large-scale thermal power infrastructure) where un-planned production halts must be completely eliminated.
- Fire and Gas Protection (F&G): Aggregating zone gas/flame diagnostic instrumentation to trip local suppression hardware or fire containment structures.
- No Internal Firmware: The T9300 hardware itself contains no microprocessor, no ROM, and no flashable firmware code.
- Target of System Flash Upgrades: When a facility schedules a safety system flash update, the update actually targets the active T94xx I/O modules plugged into the T9300 slots, alongside the master T9100/T9110 processing units.
- Compatibility Validation: During major system updates, you must reference the official Rockwell Automation Safety Certificates and Clarification Revision Lists. This step checks if your underlying physical T9300 base hardware build revisions match the target safety build numbers. All validated firmware packages must be pulled from the Rockwell Automation Product Compatibility and Download Center (PCDC).
- Chassis Capacity: Each individual T9300 base unit hosts up to 3 double-width I/O module assemblies.
- Hardware Addressing: In logic structures, any field point maps back to a strict "Bus Number - Slot Number - Channel Number" coordinate (e.g., 1-01 marks slot 1 on the primary I/O bus row).
- Build the Hardware Tree: Within the Hardware Configuration panel of your workstation, map out the central controller, and then attach T9300 I/O Base Unit slots to mirror your exact physical cabinet placement.