Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com

T8448C

/ 4.9
1001 reviews | Need a Specific Revision?
The ICS Triplex T8448C Trusted® TMR zone interface module provides a configurable interface for Fire and Gas protection systems, supporting up to 40 field device channels.
Get a quick price for T8448C
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for T8448C

  • Manufacturer:
    ICS Triplex
  • Part Number:
    T8448C
  • Product Family:
    Trusted Triple Modular Redundant
  • Product Type:
    Trusted® TMR Zone Interface Module
  • Backplane (IMB) Supply Voltage:
    20 Vdc to 32 Vdc
  • Backplane (IMB) Supply Power:
    27 W
  • Field Supply Voltage:
    18 Vdc to 32 Vdc
  • Field Supply Current:
    2 A per channel maximum (3).
  • Module Location:
    T8100, T8300 I/O Module Slot
  • Power Group to Power Group Isolation:
    50 V Reinforced (continuous) (1), [Type tested at 1411 Vdc for 60 s].
  • Field Common Isolation:
    50 V Reinforced (continuous) (1) , 250 V Basic (fault) (2) , [Type tested at 2436 Vdc for 60 s].
  • Channel to Channel Isolation:
    None
  • Fusing:
    Not user serviceable
  • Number of Channels:
    40
  • Output Off State Resistance:
    33 kΩ
  • Output On State resistance:
    1.6 Ω
  • Current Rating (Continuous):
    2 A per channel maximum .
  • Minimum On State Load Current:
    50 mA
  • Field Voltage Range:
    18 Vdc to 32 Vdc
  • Measurement Range:
    0 Vdc to +32 Vdc
  • Maximum Withstanding:
    -1 to +40 Vdc
  • Maximum Capacitance:
    at least 2800 µF at 2 A
  • Turn-on/off Delay:
    5 ms
  • Impedance:
    33 kΩ
  • Analogue Resolution:
    12 Bit
  • Calibration Accuracy:
    0 V to VFIELD-4 V = 0.12 V, VFIELD – 4 V to VFIELD = 0.48 V
  • Safety Accuracy:
    0.25 V
  • Output Short Circuit Protection:
    Electronic latching
  • Intrinsic Safety:
    None – External barrier required
  • Operating Temperature:
    0 °C to +60 °C (+32 °F to +140 °F)
  • Storage Temperature:
    -25 °C to +70 °C (-13 °F to +158 °F)
  • Relative Humidity - Operating and Storage:
    10 % – 95 %, non-condensing
  • Weight:
    1.2 kg
  • Estimated shipping dimensions:
    30.2x26.5x3cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Certification Use Cases Protection

Features:

  • Flexible 40-channel configuration supports mixed analogue and digital I/O within a single module.
  • Triple Modular Redundant architecture ensures high fault tolerance and continuous operation.
  • Integrated diagnostics and automatic line monitoring enhance system safety and reliability.
The ICS Triplex T8448C serves as a critical interface in safety instrumented systems where Fire and Gas protection is essential for operational continuity. Industrial environments such as oil and gas facilities, chemical plants, and power generation sites rely on accurate detection and rapid response to hazardous events. By supporting up to 40 configurable channels, the module consolidates multiple signal types into a single platform, reducing system complexity. The integration with the Trusted TMR system ensures stable communication and coordinated control logic. This makes the ICS Triplex T8448C particularly suitable for applications requiring both scalability and high integrity. Its ability to manage diverse field devices strengthens overall plant safety strategies.

In practical use, the ICS Triplex T8448C provides a versatile interface for connecting detectors, sensors, and actuators through the Versatile Field Termination Assembly. Each channel can be individually defined as an analogue or digital point, allowing engineers to tailor configurations according to specific zone requirements. The module supports 4–20 mA gas detection loops, fire and heat detection circuits, and control outputs for safety equipment such as dampers and extinguishing systems. Adjustable thresholds and hysteresis enable detailed monitoring of field conditions, including fault detection and alarm differentiation. With 12-bit analogue resolution and a measurement range up to 32 Vdc, signal accuracy is maintained across varying operating conditions. These capabilities allow ICS Triplex T8448C to function as both a monitoring and control component within safety loops.

Operational reliability is reinforced by the Triple Modular Redundant design embedded in the ICS Triplex T8448C. Each channel is continuously tested through triplicated diagnostic paths, ensuring that failures are detected and managed without interrupting system performance. Features such as automatic line monitoring, electronic short-circuit protection, and Sequence of Events recording with millisecond resolution provide deeper visibility into system behavior. The module also supports hot replacement, allowing maintenance without shutting down the entire system, which is essential in continuous process industries. With operating temperatures ranging from 0 °C to +60 °C and high humidity tolerance, the module performs consistently in demanding environments. Combined with IEC 61508 SIL 3 certification, ICS Triplex T8448C delivers the level of safety and reliability required for mission-critical applications.

The T8448C ICS Triplex Trusted® TMR Zone Interface Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
ICS Triplex T8448C Trusted® TMR Zone Interface Module Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ICS Triplex T8448C Trusted® TMR Zone Interface Module Specs

General

  • Manufacturer ICS Triplex
  • Model T8448C
  • Condition New Original ready stock
  • Product Family T8448
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Safety level certification: Certified by TÜV Rheinland, Germany, conforming to the highest level of SIL 3 safety instrumented system application specifications in IEC 61508 standard.
  • Explosion-proof Area Certification: Certified by ATEX Zone 2 and IECEx for flammable and explosive hazardous locations, allowing direct installation in secondary areas of high-risk processes.
  • Classification Society Approval: Passed DNV (Det Norske Veritas) and ABS (American Bureau of Shipping) tests, approved for deployment in harsh marine environments such as offshore drilling platforms.
  • Electromagnetic Compatibility Certification: Fully meets the EU CE certification's Industrial Level 3 EMC electromagnetic interference test, maintaining zero false alarms under strong magnetic fields and radio frequency interference.
  • Refinery Hazardous Area Valve Management: Serves as a digital interlock interface for explosion-proof areas, safely acquiring and controlling the on/off status of high-risk isolation valves in the field.
  • Large Oil and Gas Pipeline Emergency Disconnection (ESD): Deployed in multiple valve zones along long-distance pipelines for remote, rapid, and safe disconnection of the main pipeline in the event of a sudden leak.
  • Chemical Plant Toxic Gas Release Detection (F&G): Connects a matrix of toxic gas transmitters within specific explosion-proof functional areas, uploading critical alarm levels and interlocking trigger logic in real time.
  • Nuclear Power Plant High-Irradiation Production Area Interconnection: Used in the distributed safety protection network of reactor perimeter buildings, serving as a data communication bridge between high-risk isolation areas and the central control room.
  • Short-circuit and overload protection: The module integrates independent current-limiting protection, automatically cutting off the circuit in the event of a short circuit in a single channel without affecting other normal areas.
  • Overvoltage clamping protection: Built-in industrial-grade TVS transient voltage suppressor effectively blocks the impact of external lightning strikes or induced surges on the internal core bus.
  • Circuit electrical isolation: Strong opto-isolation protection of up to 2.5 kVdc is provided between the field I/O side and the internal logic side of the system, completely eliminating ground potential difference interference.
  • Coating physical protection: The "C" suffix indicates that it is fully covered with conformal coating conforming to G3 standards, effectively resisting the physical corrosion of hydrogen sulfide (H2S) and high-humidity salt spray.
Description
The ICS Triplex T8448C is a high-integrity Trusted® TMR Zone Interface Module engineered to manage Fire and Gas protection zones with precision and reliability. It connects directly to the Trusted TMR system via the Inter-Module Bus, ensuring seamless communication and stable power distribution within safety-critical environments. Designed for flexibility, the module allows each of its 40 channels to be individually configured as an analogue input, digital input, or digital output.

Within the ICS Triplex T8448C, channels are organized into five isolated power groups, each containing eight channels. This structure allows users to tailor configurations based on specific zone requirements, including combining power groups or distributing reset functions across channels. The module works in conjunction with the Versatile Field Termination Assembly 8842, which provides field loop conditioning and simplifies wiring for various signal types without requiring additional external hardware.

The ICS Triplex T8448C supports a wide range of field devices, including 4–20 mA gas detectors, fire and heat detectors, and break glass units. Input channels operate as voltage analogue interfaces with 12-bit resolution, enabling accurate monitoring across a measurement range of 0 Vdc to +32 Vdc. Adjustable thresholds with hysteresis allow the system to detect multiple states such as normal operation, alarm conditions, and wiring faults, improving diagnostic capability in complex safety systems.

Reliability is ensured through the module's Triple Modular Redundant architecture, where each channel is triplicated and continuously monitored. The ICS Triplex T8448C performs automatic diagnostic tests, including voltage and current measurements, as well as detection of stuck-on and stuck-off failures. Additional features such as per-channel over-current protection, automatic line monitoring, and Sequence of Events reporting with 1 ms resolution further enhance operational safety and traceability.

The module is designed for industrial environments, operating within a temperature range of 0 °C to +60 °C and supporting humidity levels up to 95% non-condensing. With hot-replacement capability and TÜV-certified IEC 61508 SIL 3 compliance, the ICS Triplex T8448C ensures minimal downtime and meets stringent safety standards required in critical applications such as oil & gas, chemical processing, and power generation systems.
Alternative Names
T8314C T8403C T8431C T8442C T8448 T8451C T8461C T8480C
Technical notes
The ICS Triplex T8448C is a SIL 3-certified Trusted TMR zone interface module with standard conformal coating, providing 2.5 kVdc galvanic isolation to ensure safe and reliable signal conditioning in hazardous Zone 2 industrial environments.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can ICS Triplex T8448C connect directly to hazardous areas?
ICS Triplex T8448C requires external intrinsic safety barriers for hazardous environments, as direct connection is not approved.
How are field devices connected to ICS Triplex T8448C?
ICS Triplex T8448C interfaces with field devices through the Versatile Field Termination Assembly 8842, which manages loop conditioning and wiring.
Does ICS Triplex T8448C provide diagnostic capabilities?
Comprehensive diagnostics are built into ICS Triplex T8448C, including automatic testing, fault detection, and real-time monitoring of voltage and current.
What applications can ICS Triplex T8448C support in industrial systems?
ICS Triplex T8448C is widely used in Fire and Gas protection systems, handling inputs from detectors and controlling actuators such as dampers, pumps, and extinguishant release systems.