    Apter Power provides PROFIBUS PA application review, official documents, sourcing support, and quotations for ProSoft A-PAL/B.

A-PAL/B

/ 4.9
1001 reviews | Need a Specific Revision?
The ProSoft A-PAL/B PROFIBUS PA Gateway connects PROFIBUS PA DPV0/DPV1 devices with EtherNet/IP or Modbus networks and includes PA power conditioning.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for A-PAL/B
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for A-PAL/B

  • Manufacturer:
    ProSoft
  • Part Number:
    A-PAL/B
  • Product Family:
    ProSoft
  • Product Type:
    PROFIBUS PA Gateway
  • Stock:
    1
  • Ethernet Connector:
    RJ45
  • Ethernet Conductors:
    CAT5 STP/UTP
  • ARP Connections:
    20 maximum
  • TCP Connections:
    20 maximum
  • CIP Connections:
    10 maximum
  • Ethernet Rate:
    10/100 Mbps
  • Embedded Switch:
    2 Ethernet ports
  • PROFIBUS PA Connector:
    3-way terminal
  • PA Master Support:
    DPV0; DPV1 Class 1 and Class 2; DPV1 alarming
  • Maximum PA Slaves:
    32
  • PA Network Isolation:
    Supported
  • Power Conditioner Voltage:
    19.0 to 23.0 VDC
  • Power Conditioner Current:
    420 mA at ≤50 °C; 320 mA at ≤60 °C; 220 mA at ≤70 °C
  • Internal Termination:
    100 Ω; software enabled
  • Master Redundancy:
    Active/Standby supported
  • Power Supply:
    22 to 26 VDC; 580 mA at 24 VDC
  • Power Consumption:
    3.3 W no bus load; 14.0 W at full bus load
  • Hardware Connector:
    5-way terminal; 5.08 mm pitch
  • Conductors:
    24 to 18 AWG
  • Enclosure:
    IP20, NEMA/UL Open Type
  • Operating Temperature:
    -20 to 70 °C
  • Humidity:
    0 to 95% RH, non-condensing
  • Estimated shipping dimensions:
    149.0 x 34.0 x 116.0 mm
  • Tariff Code:
    8517623990
  • Country of origin:
    United States
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications PA Interface Power & Bus Diagnostics

Features:

  • PROFIBUS PA to EtherNet/IP or Modbus TCP/IP link
  • Up to 32 PROFIBUS PA slave devices
  • Up to 2 kilobytes of device and status data
The A-PAL/B combines a PROFIBUS PA Master, Ethernet gateway, and isolated segment power conditioner in one Series B module. Up to thirty-two PA slave devices can be connected within the documented current limit.

DPV0 exchange, DPV1 Class 1 and Class 2 messaging, alarms, and optional Active/Standby Master redundancy are supported. EtherNet/IP or Modbus communication carries selected PA device and status data to the host system.

Available conditioner current decreases as ambient temperature rises, so the field-device load must be calculated before installation. Addressing, spur wiring, internal termination, overcurrent trip, redundancy, and FDT asset-management requirements should be reviewed together.
PA segment sizing, official documents, and quotations for the ProSoft A-PAL/B PROFIBUS PA Gateway are available through Apter Power.
ProSoft A-PAL/B PROFIBUS PA Gateway Manuals, Datasheets, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ProSoft A-PAL/B PROFIBUS PA Gateway Specs

General

  • ManufacturerProSoft Technology
  • ModelA-PAL/B
  • ConditionNew Original ready stock
  • Product FamilyPA Link Series B
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

PROFIBUS PA communication resources

  • DP services: DPV0 and DPV1 services are supported
  • Device capacity: Up to thirty-two PA slave devices
  • Data capacity: Two kilobytes of device and status data
  • Master redundancy: Active/Standby Master redundancy is supported

Integrated segment power and termination

  • Power conditioner: Isolated PA power conditioner is built in
  • Overcurrent protection: Current trip protection is configurable
  • Bus termination: Internal 100-ohm terminator is software enabled
  • Output voltage: Power conditioner output is 19 to 23 VDC

Fieldbus analysis and event records

  • Packet capture: Slate captures running PROFIBUS PA packets
  • Device statistics: Global and device statistics are available
  • Event log: Non-volatile event log records operating events
  • Port mirroring: Ethernet port mirroring supports fault analysis
Description
The A-PAL/B is a ProSoft PA Link Series B gateway that interfaces PROFIBUS PA DPV0 and DPV1 with EtherNet/IP or Modbus devices. In Master operation it can exchange as much as two kilobytes of PROFIBUS PA device and status data. The PA network supports up to thirty-two slave devices. Two Ethernet ports provide Linear or Device Level Ring topology and can also be configured for port mirroring during fault analysis.

The A-PAL/B contains an isolated PROFIBUS PA power conditioner that can supply as much as 420 mA when temperature limits permit. The overcurrent trip level is configurable, and the internal 100-ohm Fieldbus terminator can be enabled through software. DPV0 data exchange, DPV1 Class 1 messaging, DPV1 Class 2 messaging, and DPV1 alarming are supported. Active/Standby PROFIBUS PA Master redundancy and FDT asset management with an available DTM are also supported.

The A-PAL/B uses Slate Configuration Utility to define the PA module, Ethernet connections, controllers, and field devices. The utility can capture PROFIBUS PA packets from the running Fieldbus for bus-behavior analysis. Global and device-specific statistics, a non-volatile event log, and NTP time synchronization provide additional fault-finding context. The 22 to 26 VDC gateway is rated for -20 to 70 °C operation, with available PA conditioner current reduced at higher ambient temperatures.
Revisions

Revision Part #

Also known as

A-PAL Ser B
A-PAL/B, Series B, Rev B
Alternative Names
A-PAL-B A PAL B APALB ProSoft A-PAL/B ProSoft Technology A-PAL/B Aparian A-PAL/B A-PAL/B Datasheet A-PAL/B Manual
Technical notes
A-PAL/B is a ProSoft PROFIBUS PA Gateway for industrial network integration. Verify protocol roles, controller compatibility, power, and environmental limits in the official documentation.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can A-PAL/B connect PROFIBUS PA devices to EtherNet/IP or Modbus?
A-PAL/B links PROFIBUS PA DPV0/DPV1 devices with EtherNet/IP or Modbus networks; verify the selected Ethernet protocol and PA configuration.
How many field devices can A-PAL/B support?
A-PAL/B supports up to thirty-two PROFIBUS PA slave devices and exchanges up to two kilobytes of device and status data.
Does A-PAL/B provide power and termination for the PA segment?
A-PAL/B includes an isolated PA power conditioner, configurable overcurrent trip, and software-enabled 100-ohm terminator; current depends on temperature.
How is A-PAL/B configured?
A-PAL/B uses Slate Configuration Utility to define PA devices, controller connections, Ethernet settings, power protection, and internal termination.
What should I check when A-PAL/B field devices are offline?
A-PAL/B troubleshooting should check segment current, ambient-temperature derating, addresses, termination, DPV0/DPV1 settings, wiring, and packet-capture statistics.
Where is the official A-PAL/B documentation?
A-PAL/B official ProSoft datasheet is the first item in the Manuals tab; follow the current PA Link/B user manual for commissioning.
What information is needed to quote A-PAL/B?
A-PAL/B enquiries should include quantity, PA device count, segment current, redundancy requirement, Ethernet protocol, certifications, and delivery destination.