Features:
- Eight channels can be assigned supported voltage or current ranges.
- Range, wiring, and load type jointly determine the output behavior.
- Per-channel diagnostics and substitute values are carried through the ET 200PA SMART station.
Siemens 6ES7650-8BK60-0AA0 turns station output data into eight analog field signals.
Its voltage and current modes use different conductor arrangements and load boundaries.
Conversion and settling times separate controller update speed from the response of the connected load.
The 6ES7650-8BK60-0AA0 article is the eight-output ET 200PA SMART version and requires the documented IM 650-8PH station connection.
Siemens 6ES7650-8BK60-0AA0 ET 200PA SMART 8-Channel Isolated Analog Output Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Voltage and Current Ranges
- Voltage: Three bipolar or unipolar voltage ranges are selectable.
- Current: Three bipolar or unipolar current ranges are selectable.
- Resolution: The selected range determines 11-bit or 12-bit conversion.
- Project: The controller representation and receiving device must use the same range.
Load Connection Rules
- Voltage channel: Use the documented four-wire voltage connection.
- Current channel: Use the documented two-wire current connection.
- Cable: Shielded field cable is specified up to 200 m.
- Connector: The module requires the specified 40-pole front connector.
Conversion and Settling
- Conversion: The module converts a channel value in 0.8 ms.
- Resistive: A resistive load settles in the documented 0.2 ms.
- Capacitive: Voltage settling extends to 3.3 ms with capacitive loading.
- Inductive: Current settling depends on the configured inductive load range.
Fault and Substitute Behavior
- Parameterization: Diagnostics are enabled per channel in the station project.
- Voltage fault: Short-circuit protection limits a voltage-output fault.
- Current fault: Open-load behavior is checked against the current-loop wiring and load.
- Substitute value: Each channel can apply its configured value after a station fault.