Features:
- The IM 467 adds a dedicated PROFIBUS DP master interface to an S7-400 central rack.
- Up to 96 DP slaves can exchange as much as 4 KB of input and 4 KB of output data.
- Stored CPU configuration permits module replacement without a separate programming device.
By providing its own master interface, Siemens 6ES7467-5GJ02-0AB0 separates high-capacity PROFIBUS DP traffic from the remaining S7-400 communication workload.
The 6ES7467-5GJ02-0AB0 supports rates through 12 Mbit/s and applies defined limits to slave count, per-slave data, and consistent transfers.
For maintenance, 6ES7467-5GJ02-0AB0 configuration is stored in the CPU, but the module must be removed or inserted only while the station is de-energized.
The Siemens 6ES7467-5GJ02-0AB0 IM 467 PROFIBUS DP Master Interface Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7467-5GJ02-0AB0 IM 467 PROFIBUS DP Master Interface Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Master-System Capacity
- Slave count: One module can control up to 96 PROFIBUS DP slaves.
- Input volume: The master system supports up to 4 KB of input data.
- Output volume: The master system supports up to 4 KB of output data.
- Slave payload: A single slave can exchange as much as 244 bytes.
Cyclic and Consistent Transfer Limits
- Consistent block: Up to 128 bytes can be transferred consistently.
- Process directions: Input and output capacities are budgeted independently.
- Bus speed: Network rate is configurable from 9.6 kbit/s through 12 Mbit/s.
- Diagnostics: Thirty-two diagnostic connections plus one additional connection are available.
Engineering and Replacement
- Engineering tool: Configuration requires STEP 7 V5.0 or a later supported release.
- Parameter storage: Module configuration is retained in the S7-400 CPU.
- Replacement: A matching module can receive its configuration without a programming device.
- Power isolation: Removal and insertion are permitted only with the station de-energized.
Central-Rack Integration Rules
- Rack location: The interface module is installed in the S7-400 central rack.
- Module quantity: Up to four IM 467 modules are allowed per central rack.
- Slot rules: The documented module does not impose special slot rules.
- Combination limit: The IM 467 must not be operated together with CP 443-5 Extended in the same station.