Features:
- Bus Type: single ER bus
- Node Role: remote FIO node
- Power Configuration: dual-redundant
This ordering code identifies single-ER-bus remote node with redundant power modules, 100-120 V AC input, and basic non-explosion configuration.
An EB401 master in the local node connects the remote rack and its supported field I/O.
Install EB401 in the documented odd-numbered slot and observe remote-node, module, and /NDEL limits.
Availability of ANR10S-415 is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Yokogawa ANR10S-415:
Yokogawa ANR10S-415 Specifications
General
- ManufacturerYokogawa
- ModelANR10S-415
- ConditionNew and factory sealed
- Product FamilyCentum CS-Centum VP
- Location: remote from the local ESB node
- Bus: single ER-bus communication
- Capacity: up to eight FIO modules
- Master: EB401 installs in the local node or compact FCU
- Placement: use an odd-number slot for a single master
- Spacing: leave the adjacent right slot empty
- Consumption: 200 VA maximum at 100-120 V AC
- Weight: approximately 10 kg including eight I/O modules
- Connector: use the official ER Bus connection hardware