Features:
- The BRAIN-output M-capsule configuration uses the 1 to 100 kPa (4 to 400 inH2O) capsule, horizontal piping with left-side high pressure and 1/2 NPT female, two entries with blind plug.
- The BRAIN-output M-capsule configuration provides 4–20 mA DC with digital communication through BRAIN protocol, with digital indicator.
- The BRAIN-output M-capsule configuration combines 1/2 NPT female process connectors, S-code wetted assembly with Hastelloy C-276 diaphragm and 304 SST flat 2-inch pipe bracket.
For EJA110E-DMS4G-917DB, the order code combines BRAIN output rather than HART, with 316L bolting as one matched configuration.
It measures differential and static pressure for engineered flow, level, density or equipment-monitoring duties, with remote access through BRAIN protocol.
Installation approval should include a documented check of BRAIN-versus-HART electronics, host tools or bolt material and the connected system.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Yokogawa EJA110E-DMS4G-917DB:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- The BRAIN-output M-capsule configuration measures differential pressure across a primary flow element, filter, heat exchanger or vessel connection.
- The BRAIN-output M-capsule configuration supports inferred flow, level or density calculations when the impulse-piping and manifold design are validated.
- The BRAIN-output M-capsule configuration provides differential and static-pressure information for process control, protection or condition monitoring.
- The suffix defines horizontal piping with left-side high pressure, so impulse piping must preserve the designated high-pressure side.
- The mounting hardware selection is 304 SST flat 2-inch pipe bracket, and the process connection is 1/2 NPT female process connectors.
- In the documented installation context, after mechanical work, perform leak testing, zero trim and loop verification without exceeding the capsule limits.
- Certification status is controlled by the complete option suffix: No additional option suffix is included in this order code.
- The base enclosure provides IP66/IP67, Type 4X, but hazardous-area acceptance also requires the matching approval nameplate.
- Entity parameters, ambient limits and associated apparatus must be verified from the applicable certificate before energization.
- Configuration tools must recognize the EJA110E DPharp EJA Series device description and the selected BRAIN protocol signal type.
- When reviewing interoperability, the analog loop remains available to a compatible control input while digital variables use the same pair of conductors.
- In the documented interoperability context, host alarm handling must be mapped to the transmitter diagnostics without overriding the plant trip philosophy.