Features:
- The K1-treated configuration without an integral indicator uses the 1 to 100 kPa (4 to 400 inH2O) capsule, horizontal piping with left-side high pressure and 1/2 NPT female, two entries with blind plug.
- The K1-treated configuration without an integral indicator provides 4–20 mA DC with digital communication through HART 5/HART 7 protocol, with no integral indicator.
- The K1-treated configuration without an integral indicator combines 1/4 NPT female cover-flange pressure ports without separate process connectors, S-code wetted assembly with Hastelloy C-276 diaphragm and 304 SST flat 2-inch pipe bracket.
The supplied EJA110E-JMS5J-917NB/K1 variant is distinguished by oil-prohibited K1 treatment and absence of an integral indicator.
It measures differential and static pressure for engineered flow, level, density or equipment-monitoring duties, with remote access through HART 5/HART 7 protocol.
Match cleanliness treatment, absent display or cover-flange process ports to the existing assembly before wiring, pressurization or actuator movement.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Yokogawa EJA110E-JMS5J-917NB/K1:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- The K1-treated configuration without an integral indicator measures differential pressure across a primary flow element, filter, heat exchanger or vessel connection.
- The K1-treated configuration without an integral indicator supports inferred flow, level or density calculations when the impulse-piping and manifold design are validated.
- The K1-treated configuration without an integral indicator provides differential and static-pressure information for process control, protection or condition monitoring.
- The process assembly combines a 1 to 100 kPa (4 to 400 inH2O) capsule, 1/4 NPT female cover-flange pressure ports without separate process connectors and S-code wetted assembly with Hastelloy C-276 diaphragm for the stated service.
- When reviewing integration, the control-system interface is 4–20 mA DC with HART 5/HART 7 digital communication, using a total loop-load range of 0 to 1290 Ω, with 250 to 600 Ω required for digital communication.
- In the documented integration context, engineering units, damping and alarm direction must match the receiving system database before handover.
- For standards, applicable family standards include EN 61326 EMC, EN 61010 safety and EN IEC 63000 RoHS documentation.
- When reviewing standards, the IP66/IP67, Type 4X enclosure classification assumes the official cover, plug and cable-entry installation practices.
- Process-pressure work must follow the site's piping code together with Yokogawa's limits for the 1 to 100 kPa (4 to 400 inH2O) capsule.
- The selected capsule supports a calibrated span of 1 to 100 kPa (4 to 400 inH2O) within a configurable range of -100 to 100 kPa.
- When reviewing configuration, linear or square-root output, damping, engineering units and alarm direction are set through the supported interface.
- In the documented configuration context, the absence of an integral indicator means local range-setting access is unavailable at the installed instrument.