Features:
- Accepts sixteen isolated 4 to 20 mA inputs with a 40 ms update period.
- Supports individually selected two-wire or four-wire transmitter connections.
- Provides ISA G3 environmental construction for operation from -20 to +70 deg C.
This execution uses a signal-cable interface adapter and does not include explosion protection or standard HART communication. The sixteen channels share the documented module-isolation architecture.
Process current is converted and refreshed for use by the ProSafe-RS safety logic while the module provides transmitter supply within the stated electrical limits. An identical additional module can be used for redundancy.
Barrier selection and adapter-pin settings must be checked for every channel. Zener barriers are prohibited, and installations requiring intrinsic-safety separation must use an appropriate isolation barrier.
Apter Power confirms supply after the suffix, barrier method and redundancy arrangement are reviewed.
Verified resources for Yokogawa SAI143-S63:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Acquires safety-related 4 to 20 mA measurements from process transmitters.
- Supports redundant analog input arrangements in ProSafe-RS instrumented functions.
- Provides isolated signal collection in ISA G3 environments where conventional transmitters are used.
- The documented operating range for the -S63 environmental execution is -20 to +70 deg C.
- Accuracy drift is specified at +/-16 microampere for each 10 deg C temperature change.
- Cabinet thermal design must keep the installed module within its stated operating boundary.
- Input-to-system withstand capability is 1.5 kV AC for one minute.
- Zener barriers are not permitted, so isolation barriers must be selected where segregation is required.
- The suffix execution does not include explosion protection and must be applied accordingly.
- The module is supplied in the documented ISA Standard G3 environmental execution.
- Signal-cable connections and adapter pins must remain protected by the approved cabinet arrangement.
- The non-explosion-protected version cannot be placed in a hazardous area without suitable external protection.