1001 reviews | Need a Specific Revision?
Yokogawa EJA110E-JHS5J-917DB is an H-capsule differential-pressure configuration with cover-flange pressure ports and a digital indicator for differential-pressure, flow, level or density measurement.
In Stock
Ships by Friday, October 30
Fast Shipping Available
Get a quick price for EJA110E-JHS5J-917DB
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for EJA110E-JHS5J-917DB

  • Manufacturer:
    Yokogawa
  • Part Number:
    EJA110E-JHS5J-917DB
  • Product Family:
    Yokogawa DCS system
  • Product Type:
    Differential Pressure Transmitter
  • Stock:
    1
  • Measurement / Function:
    differential pressure and static pressure
  • Output / Command Signal:
    4–20 mA DC with digital communication
  • Communication / Control Interface:
    HART 5/HART 7 protocol
  • Selected Span / Torque Class:
    5 to 500 kPa (20 to 2000 inH2O)
  • Configurable Range / Travel:
    -500 to 500 kPa
  • Process / Pneumatic Connection:
    1/4 NPT female cover-flange pressure ports without separate process connectors
  • Wetted / Service Materials:
    S-code wetted assembly with Hastelloy C-276 diaphragm
  • Bolting / Mechanical Interface:
    B7 carbon steel bolts and nuts
  • Installation Arrangement:
    Horizontal piping with left-side high pressure
  • Housing:
    Cast aluminum amplifier housing
  • Electrical Connection:
    1/2 NPT female, two entries with blind plug
  • Local Indicator:
    Digital indicator
  • Mounting Hardware:
    304 SST flat 2-inch pipe bracket
  • Ordering Options:
    No additional option suffix is included in this order code.
  • Degree of Protection:
    IP66/IP67, Type 4X
  • Ambient Conditions:
    -40 to 85°C (-40 to 185°F), or -30 to 80°C with LCD
  • Process / Service Temperature:
    -40 to 120°C (-40 to 248°F)
  • Communication Load / I/O:
    a total loop-load range of 0 to 1290 Ω, with 250 to 600 Ω required for digital communication
  • Stability / Control Performance:
    M/H/V stability ±0.1% of URL for 10 years; F ±0.2% per year
  • Manufacturer Reference:
    Yokogawa GS 01C31B01-01EN
  • Tariff Code:
    9026201090
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Applications Environmental Ratings Compliance Communication

Features:

  • The H-capsule cover-flange configuration uses the 5 to 500 kPa (20 to 2000 inH2O) capsule, horizontal piping with left-side high pressure and 1/2 NPT female, two entries with blind plug.
  • The H-capsule cover-flange configuration provides 4–20 mA DC with digital communication through HART 5/HART 7 protocol, with digital indicator.
  • The H-capsule cover-flange configuration combines 1/4 NPT female cover-flange pressure ports without separate process connectors, S-code wetted assembly with Hastelloy C-276 diaphragm and 304 SST flat 2-inch pipe bracket.
Use the full EJA110E-JHS5J-917DB code when matching the configuration defined by H capsule with cover-flange pressure ports and digital indication.

It measures differential and static pressure for engineered flow, level, density or equipment-monitoring duties, with remote access through HART 5/HART 7 protocol.

The replacement review must resolve cover-flange ports, H capsule or impulse-piping layout before the equipment is returned to service.

Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Yokogawa EJA110E-JHS5J-917DB: Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • The H-capsule cover-flange configuration measures differential pressure across a primary flow element, filter, heat exchanger or vessel connection.
  • The H-capsule cover-flange configuration supports inferred flow, level or density calculations when the impulse-piping and manifold design are validated.
  • The H-capsule cover-flange configuration provides differential and static-pressure information for process control, protection or condition monitoring.
  • The assembled housing is rated IP66/IP67, Type 4X when covers, plugs and the 1/2 NPT female, two entries with blind plug entry are correctly sealed.
  • When reviewing environmental ratings, the rating does not extend to an incorrectly fitted process connector or an open conduit path.
  • In the documented environmental ratings context, any approval suffix, coating option or stainless housing selection must be read from the complete order code before installation.
  • For compliance, the transmitter family is designed to the applicable EN 61010 safety and EN 61326 EMC requirements listed by Yokogawa.
  • When reviewing compliance, installed compliance depends on retaining the IP66/IP67, Type 4X enclosure, approved entries and specified process materials.
  • In the documented compliance context, any hazardous-location claim must be supported by the exact option suffix and matching nameplate rather than the base family alone.
  • The selected electronics carry HART 5/HART 7 protocol data on the documented 4–20 mA DC with digital communication measurement loop.
  • Digital communication is commissioned within a total loop-load range of 0 to 1290 Ω, with 250 to 600 Ω required for digital communication; verify the exact loop voltage at the transmitter terminals.
  • Remote parameter access must use a host and device description that support the EJA110E DPharp EJA Series communication revision.
Description
EJA110E-JHS5J-917DB defines a single purchasable EJA110E differential pressure transmitter variant. The relevant suffix details are H capsule with cover-flange pressure ports and digital indication.

It measures differential and static pressure for engineered flow, level, density or equipment-monitoring duties, with remote access through HART 5/HART 7 protocol. The configuration is intended for differential-pressure measurement across primary elements, filters, heat exchangers or vessels when the process and installation limits are satisfied.

For an exact spare, reconcile the nameplate with the instrument index and connection drawing. The main mismatch risk is cover-flange ports, H capsule or impulse-piping layout.
Alternative Names
EJA110E-JHS5J-917DB Yokogawa EJA110E-JHS5J-917DB EJA110E JHS5J 917DB EJA110EJHS5J917DB Yokogawa EJA110E Differential Pressure Transmitter Yokogawa EJA110E-JHS5J-917DB Differential Pressure Transmitter Yokogawa DPharp EJA EJA110E-JHS5J-917DB
Technical notes
Verify cover-flange port orientation and manifold equalization before applying pressure; reversing the high side changes the sign of the measured differential.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What enclosure protection is specified for EJA110E-JHS5J-917DB?
The documented EJA-E housing protection is IP66/IP67 and Type 4X when all covers, cable entries and seals are installed in accordance with the official instructions.
Which side of EJA110E-JHS5J-917DB must receive the high-pressure impulse line?
The ordered horizontal-piping arrangement places the high-pressure side on the left. Reversing the lines changes sign and can defeat the configured measurement or alarms.
What higher-differential duties can use EJA110E-JHS5J-917DB?
It can support engineered flow, level or equipment pressure-drop measurement where the required span is within the H-capsule capability and static-pressure limits.
How should the seller document the condition of EJA110E-JHS5J-917DB cover-flange ports?
Request close photographs showing clean, undamaged 1/4 NPT female ports and sealing surfaces, plus disclosure of any installed adapters or protective plugs.
What bolting check is essential before installing EJA110E-JHS5J-917DB as a spare?
Confirm that the offered B7 bolting is acceptable for the process, ambient temperature and site corrosion rules; a different bolt material requires an engineering review.
Which proof-test information should be requested with EJA110E-JHS5J-917DB documentation?
State the safety or control function, proof-test interval and required alarm behavior, then request the official instruction manual and configuration records needed by the site's procedure.