1734-IT2I

/ 4.9
1001 reviews | Need a Specific Revision?
Allen-Bradley 1734-IT2I is a two-channel individually isolated POINT I/O thermocouple input module with cold-junction compensation support.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for 1734-IT2I
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 1734-IT2I

  • Manufacturer:
    Allen-Bradley
  • Part Number:
    1734-IT2I
  • Product Family:
    Point I/O 1734
  • Product Type:
    POINT I/O 2-Channel Isolated Thermocouple Input Module
  • Stock:
    1
  • Inputs:
    2 differential individually isolated thermocouple channels
  • Supported types:
    B, C, E, J, K, N, R, S, T
  • Input range:
    ±75 mV
  • Resolution:
    15 bits plus sign; 2.5 µV/count
  • Cold-junction range:
    0...70 °C with 1734-RTBCJC
  • POINTBus current:
    175 mA at 5 V DC
  • Weight:
    0.036 kg
  • Estimated shipping dimensions:
    5.66x1.21x7.75cm
  • Tariff Code:
    8537101190
  • Country of origin:
    Singapore
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Cold-Junction Setup Isolated Diagnostics Product Applications

Features:

  • Isolated measurement: two differential thermocouple channels
  • Sensor breadth: nine documented thermocouple types
  • Cold-junction support: 1734-TBCJC and 1734-RTBCJC provide the recommended compensation path
1734-IT2I is intended for low-level thermocouple signals that benefit from individual channel isolation.

Temperature accuracy depends on matching sensor alloy, extension cable, polarity, cold-junction hardware, and the configured curve from probe to controller.

Commissioning should challenge both temperature conversion and the open-wire diagnostic path while recording actual tag refresh behavior.

Availability of 1734-IT2I is subject to Apter Power inventory and sourcing confirmation.
Allen-Bradley 1734-IT2I POINT I/O 2-Channel Isolated Thermocouple Input Module Manuals and Product Resources
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Allen-Bradley 1734-IT2I POINT I/O 2-Channel Isolated Thermocouple Input Module Specs

General

  • ManufacturerAllen-Bradley
  • Model1734-IT2I
  • ConditionNew Original ready stock
  • Product FamilyPOINT I/O 1734
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Preserve the reference temperature

  • Base: use 1734-TBCJC where the recommended compensation method is required.
  • RTB: verify the 1734-RTBCJC identity and seating.
  • Enable: align the cold-junction bit with installed hardware.
  • Check: compare terminal temperature and channel reading during commissioning.

Trace a thermocouple fault by channel

  • Alloy: inspect probe and extension wire for the selected type.
  • Polarity: correct reversed conductors before applying offsets.
  • Open wire: use channel status to locate a broken path.
  • Refresh: consider the approximately 25 ms fastest controller-tag update.

Supported product applications

  • Furnace monitoring: acquire supported high-temperature thermocouple types.
  • Machine heat zones: isolate two low-level sensor channels near equipment.
  • Process skids: combine cold-junction-compensated temperature inputs with POINT I/O.
  • Maintenance retrofits: restore a documented isolated thermocouple position.
Description
1734-IT2I accepts two differential, individually isolated thermocouple inputs in a POINT I/O station. The Series C module supports Type B, C, E, J, K, N, R, S, and T sensors with 15-bit-plus-sign conversion across a ±75 mV input range.

Cold-junction compensation for 1734-IT2I is provided through the 1734-RTBCJC removable terminal block used with the 1734-TBCJC base, or through an engineered alternative described by Rockwell Automation. Per-channel filtering and open-wire status support stable temperature acquisition and fault diagnosis.

Selection of 1734-IT2I should include the thermocouple type, extension-wire alloy, polarity, isolation requirement, cold-junction method, filter, controller RPI, and acceptance temperature points. The fastest controller-tag refresh is about 25 ms even when the module detects input changes more quickly.
Revisions

Revision Part #

Also known as

1734-IT2I Series B
1734-IT2I/B, Series B
1734-IT2I Series C
1734-IT2I/C, Series C
Alternative Names
Allen-Bradley 1734-IT2I Rockwell Automation 1734-IT2I AB 1734-IT2I 1734IT2I 1734 IT2I POINT I/O isolated thermocouple input
Technical notes
For 1734-IT2I, cold-junction and thermocouple wiring choices determine measurement credibility. Verify Series C, sensor alloy and polarity, 1734-TBCJC with 1734-RTBCJC compensation, channel isolation, shield routing, notch filter, RPI-derived tag refresh, open-wire action, and the absence of input overvoltage protection before validating both channels at known temperatures.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why can 1734-IT2I display a plausible but offset temperature after terminal-base service?
Verify the 1734-RTBCJC, cold-junction enable bit, thermocouple type, extension-wire alloy, polarity, terminal temperature, and any configured offset.
What should be investigated when one 1734-IT2I channel goes to maximum temperature?
Open-wire behavior can force a high value; inspect the probe, extension cable, terminal block, cold-junction leads, and channel status before recalibration.
How does 1734-IT2I channel isolation affect a two-sensor installation?
Each differential input is individually isolated, but shield routing, sensor grounding, cable separation, and the terminal-base reference still require documented engineering.
Why may faster notch settings on 1734-IT2I not produce equally fast controller tags?
Module detection and controller refresh are different; the RPI determines EPR, and the fastest controller-tag update is approximately 25 ms.
Can 1734-IT2I use ordinary copper extension wire for every thermocouple type?
No. Match the documented thermocouple and extension-wire alloys and observe polarity; dissimilar junctions can create temperature-dependent measurement error.
What information should accompany a 1734-IT2I quotation request?
Provide Series, thermocouple types, 1734-TBCJC or compensation method, controller profile, quantity, label photos, destination, and required delivery date.