X20AI4222

/ 4.9
1001 reviews | Need a Specific Revision?
B&R X20AI4222 is a four-channel differential ±10 V analog input module with 13-bit conversion and 400 microsecond acquisition for the X20 System.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for X20AI4222
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for X20AI4222

  • Manufacturer:
    B&R
  • Part Number:
    X20AI4222
  • Product Family:
    B&R X20 System
  • Product Type:
    Analog Voltage Input Module
  • Stock:
    1
  • Analog inputs:
    4 differential voltage inputs
  • Input range:
    ±10 V
  • Digital converter resolution:
    ±12-bit (13-bit including sign)
  • Conversion time:
    400 µs for all inputs
  • Input impedance:
    20 MΩ
  • Permissible input signal:
    Maximum ±30 V
  • Input protection:
    Protection against wiring with supply voltage
  • Input filter:
    Third-order low-pass, 1 kHz cutoff
  • Common-mode range:
    ±12 V
  • Common-mode rejection:
    70 dB at DC and 50 Hz
  • Required terminal block:
    X20TB12, ordered separately
  • Compatible bus modules:
    X20BM11 or X20BM15, ordered separately
  • Degree of protection:
    IP20
  • Operating temperature:
    -25 to 60 °C horizontal; -25 to 50 °C vertical
  • Dimensions:
    1.25 × 5.3 × 9.8 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    ​Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Wiring Diagnostics Integration Application
  • Measures four differential ±10 V analog channels
  • Converts all inputs in 400 microseconds with 13-bit resolution
  • Includes a 1 kHz input filter, configurable overload values, and wiring protection

X20AI4222 is a B&R analog voltage input module designed for X20 System I/O stations.

The module expands an X20 station with four voltage-measurement channels for standard analog feedback and command signals.

Before installation or replacement, verify the complete material number, the ±10 V signal range, differential wiring, common-mode voltage, source impedance, scaling, overload handling, X20TB12, X20BM11 or X20BM15, grounding, and project mapping.

Availability, condition, price, and shipping time for X20AI4222 are confirmed during quotation.

B&R X20AI4222 Analog Voltage Input Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Each input uses a differential signal connection
  • All channels share the same non-isolated analog group even though the group is isolated from the bus
  • Common-mode voltage must remain within the documented range
  • Input and module status are available through indicators and software
  • The controller can receive a configurable value during overload
  • Supply-wiring protection does not replace correct signal and grounding design
  • X20TB12 provides the required 12-pin 24 VDC-keyed terminal connection
  • X20BM11 or X20BM15 provides the compatible X20 bus connection
  • Engineering-unit scaling and fault handling are configured in the controller project
  • Four-channel ±10 V sensor and transducer acquisition
  • Analog feedback measurement from drives or machine devices
  • Distributed voltage monitoring in X20 control stations
Description
X20AI4222 is a B&R analog voltage input module for the X20 System distributed I/O platform.

It measures four differential ±10 V channels with 13-bit conversion, a 1 kHz third-order input filter, configurable overload values, and supply-wiring protection.

Before installation or replacement, confirm the complete material number, the ±10 V signal range, differential wiring, common-mode voltage, source impedance, scaling, overload handling, X20TB12, X20BM11 or X20BM15, grounding, and project mapping.
Alternative Names
X20AI4222 X20 AI 4222 X20-AI4222 B&R X20AI4222 BR X20AI4222 B&R X20 AI 4222 X20 System X20AI4222
Technical notes
X20AI4222 is a four-channel ±10 V input module and does not provide current-input mode; verify differential wiring, ±12 V common-mode range, scaling, overload handling, X20TB12, and saved channel mapping before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can B&R X20AI4222 measure 0 to 20 mA signals?
No. X20AI4222 is documented for ±10 V voltage inputs; select a current-capable module when a current loop must be connected directly.
Are B&R X20AI4222 inputs single-ended or differential?
They are differential inputs. Wire both signal conductors as documented and keep common-mode voltage within range.
Why can B&R X20AI4222 show an overload value below the wiring-protection limit?
The valid measuring range and the absolute permissible input limit are different. Values outside ±10 V can be out of measurement range even though protection has not yet been exceeded.
How should unused B&R X20AI4222 channels be handled?
Configure and terminate unused channels according to the project and noise environment so that floating signals do not create misleading diagnostics or values.
Are the four B&R X20AI4222 channels isolated from each other?
No. The analog group is isolated from the bus, but the channels are not isolated from one another.
Which accessories are required for B&R X20AI4222?
Order an X20TB12 terminal block and a compatible X20BM11 or X20BM15 bus module separately.
What should be verified before replacing B&R X20AI4222?
Verify channel polarity, terminal mapping, grounding, common-mode voltage, scaling, overload behavior, accessories, and saved Automation Studio configuration.